20
Each zone input can use a different input configuration. To program a large number of zones with a
certain configuration use the Multiple Selection feature in the Protégé® System Management Suite
application.
When using the No Resistor configuration, the Protégé® SE Integrated System Controller
only
monitors the opened and closed state of the connected input device generating the alarm and seal
conditions.
Figure 22 - No EOL Resistor Zone Configuration
+A
UX
-
Z1
COM
CO
M
Z2
Z3
Z4
N.C Zone Contact
6.2 Resistor Value Options
When using the EOL resistor configuration, the EOL resistor option must be configured based on
the site requirements. Note that not all resistor options are supported on all Protégé® field
modules.
(Refer to Zones Section in the Protégé® Reference Manual).
Value 1
Value 2
Monitored Status
1k
1k
Open, Closed, Tamper, Short
1k
-
Open, Closed
<5K7
-
Open, Closed
No Resistors
-
Open, Closed
2k2
6k8
Open, Closed, Tamper, Short
10k
10k
Open, Closed, Tamper, Short