background image

Protégé® SE Integrated System Controller

Installation Manual

PR

T-C

TRL-SE

PENDING

Содержание PRT-CTRL-SE

Страница 1: ...Protégé SE Integrated System Controller Installation Manual PRT CTRL SE PENDING ...

Страница 2: ...ransmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Integrated Control Technology Limited Designed and manufactured by Integrated Control Technology Limited Protégé and the Protégé Logo are registered trademarks of Integrated Control Technology Limited All other brand or product names are trademarks or registered trademarks of t...

Страница 3: ... 11 4 9 Expansion Connector 12 4 10 Ethernet 10 100 Network Interface 13 5 0 Door Access Control 14 5 1 Card Reader Connection 14 5 2 Multiple Wiegand Card Reader Connection 15 5 3 Door Contact Connection 16 5 4 Lock Output Connection 17 5 5 Programming the Onboard Reader 18 6 0 Inputs 19 6 1 Zones 19 6 2 Resistor Value Options 20 6 3 Trouble Zones 21 7 0 Programmable Outputs 22 7 1 Bell Siren PGM...

Страница 4: ...Network RX TX Indicators 27 9 9 Ethernet Link Indicator 27 9 10 100Mb Indicator 27 9 11 R1 R2 Data Indicators 27 9 12 Online Indicator 27 10 0 Mechanical Diagram 28 11 0 Mechanical Layout 29 12 0 System Capacities 30 13 0 Technical Specifications 31 13 1 Current and Validation Example 1 32 13 2 Current and Validation Example 2 33 13 3 Current and Validation Example 3 34 14 0 Ordering Information 3...

Страница 5: ...e Internal industry standard 10 100 Ethernet 32 Bit advanced RISC processor with 2MB RAM and 4MB flash 16x high security monitored zone inputs NIST Certified AES 256 Bit Encryption When receiving the Protégé SE Integrated System Controller you should find the kit contains the items listed below The kit type is clearly labelled on the packaging and will tell you what your kit contains Please note t...

Страница 6: ...are listed below Visit www incontrol co nz for the latest Protégé Module and product information Product Code Description PRT CTRL SE Protégé SE Integrated System Controller PRT CTRL LE Protégé LE Integrated System Controller PRT TLCD Protégé Touchscreen Keypad PRT ATH1 Protégé Temperature and Humidity Sensor PRT KLCD Protégé Alphanumeric LCD Keypad PRT ZX16 PCB Protégé 16 Zone Input Expander PRT ...

Страница 7: ...lculate the location and position of the cabinet enclosure and mark the holes for the keyhole points in the top left and right locations This will allow you to screw in the screws and then hang the box on them adjusting the location to suit Step 3 Ensure a solid fixing point and screw in the two screws Before tightening the top screws insert the tamper bracket in the slot provided on the right sid...

Страница 8: ...ection in the installation A minimum 14AWG solid copper wire should be used from the Protégé SE Integrated System Controller s earth connection point to the clamp on the cold water pipe If other earth clamps are present at the same connection point connect the clamp below the existing units Figure 1 Tamper Input Connection Figure 2 Earth Ground Connection The telephone communication dialer contain...

Страница 9: ...et enclosure In this case wire the electrical circuit to the electrical termination point inside the cabinet enclosure and the secondary wires of the transformer to the AC Input on the Protégé SE Integrated System Controller The earth wire should be routed to the terminal on the Protégé SE Integrated System Controller when using an internal transformer Termination of wiring to the Protégé SE Integ...

Страница 10: ...ne The next dynamic battery test will occur 30 minutes after AC power has been restored This delay allows the battery to achieve optimal charging during the first 30 minutes that power has been restored to the unit Once the first test is completed the dynamic testing will return to the programmed value default 10 minutes When power is first applied to the Protégé SE Integrated System Controller a ...

Страница 11: ...gure the Protégé SE Integrated System Controller manually for the charge current select the appropriate battery current limit setting using the jumpers as shown in figure 5 below Figure 5 Battery Charge Jumper Figure 6 Jumper Location 350mA 700mA ...

Страница 12: ...ollowing diagram Figure 8 Standard Communication Connection 4 6 Status Indicator The Status Output will activate according to the status indicator on the Protégé SE Integrated System Controller and can be used to provide signalling or indication of the Protégé SE Integrated System Controller status outside the enclosure The following diagrams show the connection of an LED indicator to the Status O...

Страница 13: ...o only use this connection for smaller systems where limited power is required For larger installations use a separate power supply NA N N NB NA N N NB NA N N NB AUX Z13 COM COM Z14 Z15 Z16 Protégé SE Integrated System Controller or module supplying power to networked devices AUX power from Module or external power supply Next modules on network EOL OFF EOL ON The EOL End Of Line jumper setting mu...

Страница 14: ...E Integrated System Controller using the onboard telephone connection terminals Figure 11 Telephone Line Connection It is recommended that the earth connection for the telephone and main power supply refer to the section Earth Ground Connection on page 5 earth be run separately and should be terminated on the cold water pipe or similar grounding point within the installation R1i T1i T1o R1o Telco ...

Страница 15: ...re that the plastic mounting hardware provided is correctly inserted from the rear of the Protégé SE Integrated System Controller Pay attention to the key location of the 40 Way Connector Figure 12 Expansion Connector and Mounting Hole Location Figure 13 Connection and Mounting Power to the Protégé SE Integrated System Controller must be turned off when connecting any hardware or system device to ...

Страница 16: ...t hub or switch Temporary direct connections can be used for onsite programming by connecting directly to the computer Ethernet port Installing the Protégé SE Integrated System Controller on an active network requires knowledge of the configuration and structure for the network Always consult the network or system administrator and ask them to provide you with a fixed IP address that can be assign...

Страница 17: ... Exit mode 2 Doors 2 Readers The shield connection on the card reading device that is connected to the Protégé SE Integrated System Controller port should not be connected to a AUX or 0V connection Do not join the shield and black wires at the card reading device The shield should not be connected to any shield used for isolated communication Always refer to the card reader manufacturer for detail...

Страница 18: ...cted to the Protégé SE Integrated System Controller port should not be connected to a AUX or 0V connection Do not join the shield and black wires at the card reading device The shield should not be connected to any shield used for isolated communication Always refer to the card reader manufacturer for detailed installation guidelines The reader that is multiplexed in to the alternate reader port w...

Страница 19: ... in the onboard reader set up Figure 18 Door Contact Connection Zone Access Control Function Default Setting Zone 9 Door Contact Port 1 Door Contact Port 1 Zone 10 REX Input Port 1 REX Input Port 1 Zone 11 Bond Sense Port 1 General Purpose Zone Zone 12 REN Input Port 1 General Purpose Zone Zone 13 Door Contact Port 2 Door Contact Port 2 Zone 14 REX Input Port 2 REX Input Port 2 Zone 15 Bond Sense ...

Страница 20: ... maximum current on the controller outputs is not recommended Ensure the devices connected to the outputs are within the limits as detailed in the Technical Specifications section on page 31 As indicated in figure 19 the Lock Outputs are shared with the Bell Siren functions You are able to select another output for the Lock Control P3 or P4 if the Bell Siren function is required To use the lock ou...

Страница 21: ...The onboard reader uses zone inputs 9 12 and 13 16 as it s door contact REX bond sense and REN inputs respectively Any of these inputs that are not configured for use with the Onboard Reader may be used as general purpose zone inputs The default settings are shown in the following table To enable or disable the onboard reader inputs use the reader expander properties box in the Protégé Software as...

Страница 22: ...ne inputs by using the expansion modules The Protégé SE Integrated System Controller can monitor the state of up to 16 zone inputs such as magnetic contacts motion detectors and temperature sensors Devices connected to these zones can be installed to a maximum distance of 300m 1000ft from the Protégé SE Integrated System Controller when using 22 AWG The Protégé SE Integrated System Controller supp...

Страница 23: ... the alarm and seal conditions Figure 22 No EOL Resistor Zone Configuration AUX Z1 COM COM Z2 Z3 Z4 N C Zone Contact 6 2 Resistor Value Options When using the EOL resistor configuration the EOL resistor option must be configured based on the site requirements Note that not all resistor options are supported on all Protégé field modules Refer to Zones Section in the Protégé Reference Manual Value 1...

Страница 24: ... Service Report Test CP001 06 Service Report Failure To Communicate Reporting Failure General CP001 07 Phone Line Fault Phone Line Lost General CP001 08 Auxiliary Failure Power Fault General CP001 09 Bell 1 Cut Tamper Bell PGM Fault General CP001 10 Bell 2 Cut Tamper Bell PGM Fault General CP001 11 Bell 1 Cut Tamper Bell PGM Fault General CP001 12 Bell 2 Cut Tamper Bell PGM Fault General CP001 13 ...

Страница 25: ...cally fused circuit and automatically shuts down under fault conditions If the load on the bell terminals returns to normal the Protégé SE Integrated System Controller reinstates power to the bell terminals on the next transition of the output When the Bell Output is not used the appropriate trouble zone will be activated refer to the Trouble Zones section on page 21 To avoid this connect a 1K res...

Страница 26: ...xceeding this amount will damage the PGM Output Figure 24 Open Collector PGM 3 4 Connection B1 B1 B2 B2 P3 P4 1K5 OHM LED AUX Z1 COM COM Z2 Z3 Z4 7 3 Reader PGMs If readers are not attached to the reader ports then the Reader 1 L1 and BZ and the Reader 2 L1 and BZ Outputs can be used as general purpose PGMs These can be controlled by assigning the RDxxxGreen R1 RDxxx Beeper R1 RDxxxGreen R2 and RD...

Страница 27: ...tches should be in the off position Switch Switch Function 1 2 Power Up Boot Mode OFF OFF Normal Operation ON OFF BOOT Loader OFF ON BIOS Utility ON ON Reserved Do Not Set Switch Switch Function 3 IP Address Configuration OFF Programmed IP Configuration ON IP Will be set to 192 168 111 222 while this switch remains on Allows the connection and review of the programmed IP address or the modificatio...

Страница 28: ...witch 4 Step 3 Power up the Protégé SE Integrated System Controller by turning on the AC supply Step 4 Turn OFF Configuration Dip Switch 4 once the Protégé SE Integrated System Controller is indicating normal status by flashing the green status indicator The system will now be defaulted with all programming and settings returned to factory configuration Defaulting the Protégé SE Integrated System ...

Страница 29: ...a battery test is in progress and that battery charging is being performed When AC is present the battery charging current will be indicated by a varying intensity level on this indicator This indicator will also illuminate when a battery test is in progress by illuminating brightly for 30 seconds every 10 minutes The battery test period is a programmable option in the Protégé SE Integrated System...

Страница 30: ...ndicator will flash for a period of 600 milliseconds when the Ethernet interface receives or sends a valid frame 9 10 100Mb Indicator The 100Mb Indicator is located next to the Ethernet connector and is labeled 100 It will be on when the network communication has been successfully negotiated to operate at 100Mbs 9 11 R1 R2 Data Indicators The R1 R2 Data Indicators are located above the Reader 1 an...

Страница 31: ...6 Mechanical Diagram 16V AC Input Isolated COMMS Mounting Holes 350mA 700mA Jumper EOL Jumper Battery Input Cabinet Tamper Input Bell Siren Outputs PGM 3 4 Outputs Zones 1 to 4 Fault Status LED Coin Cell Battery Zones 5 to 8 Zones 9 to 12 Reader Port 1 Reader Port 2 Zones 13 to 16 RS 485 Network Telephone Dialer Config Switch 10 100 Ethernet Ethernet Status LEDs Expansion Interface Part Number ...

Страница 32: ...below outlines the essential details needed to help ensure the correct installation of the Protégé SE Integrated System Controller 2mm 183mm 93 5mm 81 5mm 175mm 76 5mm 98 5mm PRT CTRL SE 112 2mm 234mm 225mm 113 6mm 5mm diameter Figure 27 Mechanical Layout ...

Страница 33: ... 8 8 8 8 4 8 4 Phone Numbers 16 16 16 16 8 8 8 Schedules 128 248 48 28 64 32 32 Holidays 32 32 32 32 32 32 8 Daylight Saving Adjustment Settings 1 1 1 1 1 1 1 Automation Points 32 32 32 32 16 248 8 Panel Configuration Information 1 1 1 1 1 1 1 Area Names 32 32 64 64 128 64 248 Access Level Names 128 248 48 32 248 64 16 Zone Type Names 64 64 32 28 248 16 16 Zone Names 464 720 68 88 1136 28 1104 Hom...

Страница 34: ...85 Communication Interface Port 12VDC 28mA Input Communication Modem 1x 2400bps Modem Communication Readers Standard Mode 2x Wiegand or clock data readers providing one Entry Exit Door or two Entry Exit only Doors Readers Multiplex reader Mode 4x Wiegand Readers connected in Multiplex Reader mode providing any combination of Entry or Exit for two Doors Zone Inputs System Zones 16x High Security Mo...

Страница 35: ...m Controller Specifications have to be validated to ensure that individual maximum currents and total combined current are not exceeded External Devices Connected to Panel 4x EDGE PIR Motion Detectors Z1 to Z4 1x 15W Siren 500mA 13 8VDC Current Consumption Total Combined Current Available 1 8A 1800mA Operating Current 280mA Typical Battery Charging 350mA Standard Current Charging DC Output Auxilia...

Страница 36: ...ed current are not exceeded External Devices Connected to Panel 8x EDGE PIR Motion Detectors Z1 to Z8 2x 15W Siren 500mA 13 8VDC Current Consumption Total Combined Current Available 1 8A 1800mA Operating Current 280mA Typical Battery Charging 350mA Standard Current Charging DC Output Auxiliary 8x EDGE PIR Motion Detectors 15mA each Total 120mA Siren on Bell 1 Output 500mA Siren on Bell 2 Output 50...

Страница 37: ...lled by P3 and P4 50mA each 1x 15W Siren 500mA 13 8VDC Current Consumption Total Combined Current Available 1 8A 1800mA Operating Current 280mA Typical Battery Charging 700mA High Current Charging DC Output Auxiliary 8x EDGE PIR Motion Detectors 15mA each Total 120mA DC Output Auxiliary 2x External Relays 50mA each Total 100mA Siren on Bell 1 Output 500mA Total Consumption 1 7A 1700mA Validation I...

Страница 38: ...nformation Please use the following product codes when placing an order for the Protégé SE Integrated System Controller PRT CTRL SE Manuals and literature are available at www incontrol co nz in the documentation section ...

Страница 39: ...eller the Seller cannot guarantee the performance of the security system Seller s obligation and liability under this warranty is expressly limited to repairing or replacing at Seller s option any product not meeting the specifications In no event shall the Seller be liable to the buyer or any other person for any loss or damages whether direct or indirect or consequential or incidental including ...

Страница 40: ...64 9 476 7124 Fax 64 9 476 7128 E mail support incontrol co nz www incontrol co nz Designers and manufacturers of integrated electronic access control security and building automation products Designed and manufactured by Integrated Control Technology Limited Copyright Integrated Control Technology Limited 2003 2010 All rights reserved ICT CODE 245 4045 001 V A0C6 ...

Отзывы: