Configure the MNET Server Module
6201-WA-MNET
♦
ProLinx Wireless
High Speed Wireless Modbus TCP/IP Gateway
ProSoft Technology, Inc.
Page 29 of 48
June 27, 2007
This command states:
Receive 600 words of data with each exchange ID = 1002 from IP:
172.16.10.130 and place them in 600 registers beginning at database register
1200. Receive data within 400 ms using UNICAST.
The second Consume command is set up the same way. It must correspond to
the second Produce command in order to accept the data coming from it.
Referring to the MNET Client PWP Exchanges section, the
MNET Client
also
had two Consume commands. These commands are as follows:
This first command states:
Receive 600 words of data with exchange ID = 1002 from IP 172.16.10.130, and
place them in 600 registers beginning at database register 0. This command will
wait up to 400 milliseconds for the data.
The second Consume command is set up the same way. It must correspond to
the second Produce command from the MNET Server in order to accept the data
coming from it.
We now need to build the first Produce commands on the
MNET Server
to
correspond with the first Consume commands on the MNET Client. The
corresponding command looks like this:
This command states:
Send 600 words of data beginning at data register 0 to 172.16.10.130 (the MNET
Client) using an exchange ID of 1000. Send data every 100 ms using UNICAST.
Both the MNET Server and the MNET Client have corresponding Produce and
Consume commands. The following diagram illustrates the sample application: