6201-WA-MNET
♦
ProLinx Wireless
Configure the MNET Server Module
High Speed Wireless Modbus TCP/IP Gateway
Page 28 of 48
ProSoft Technology, Inc.
June 27, 2007
This section is used to synchronize the time using a centralized atomic clock.
This feature is only usable if your modules are communicating through an access
point such as a RadioLinx Industrial Hotspot. The values in this window should
be left with the default values. As you select each parameter, the help window on
the screen displays information to help you make your selections. The PWP
Driver Manual located on the ProLinx Solutions CD describes each parameter in
detail.
4.1.4
Radio PWP Exchanges
Double-click on the
icon.
The commands in this section correspond to commands set up in the MNET
Client module. For example, the MNET Client module has a Produce command
to send data to the MNET Server. The MNET Server must have a corresponding
Consume command to match up with the MNET Client Produce command in
order to accept the MNET Client produced data.
If you remember the example in the
MNET Client
section, the first Produce
command (on line 3) is as follows.
This command states:
Send 600 words of data beginning at data register 1200 to 172.16.10.131 (the
MNET Server) using an exchange ID of 1002. Send data within 100 ms using
UNICAST.
We now need to build the Consume command on the
MNET Server
in order to
accept the data. The corresponding Consume command on the MNET Server
looks like this: