Configuring the MVI56E-MCMR Module
MVI56E-MCMR ♦ ControlLogix Platform
User Manual
Modbus Communication Module with Reduced Data Block
Page 92 of 223
ProSoft Technology, Inc.
2.7
Downloading the Project to the Module
Note: For alternative methods of connecting to the module with your PC, refer to Using CIPconnect
to Connect to the Module (page 94) or Using RSWho to Connect to the Module (page 104).
In order for the module to use the settings you configured, you must download
(copy) the updated Project file from your PC to the module.
1
In the tree view in
ProSoft Configuration Builder
, click once to select the
MVI56E-MCMR
module.
2
Open the
P
ROJECT
menu, and then choose
M
ODULE
/
D
OWNLOAD
.
This action opens the
Download
dialog box. Notice that the Ethernet address
field contains the temporary IP address you assigned previously.
ProSoft
Configuration Builder
will use this temporary IP address to connect to the
module.
Click
T
EST
C
ONNECTION
to verify that the IP address allows access to the
module.
3
If the connection succeeds, click
D
OWNLOAD
to transfer the Ethernet
configuration to the module.