Configuring the MVI56E-MCMR Module
MVI56E-MCMR ♦ ControlLogix Platform
User Manual
Modbus Communication Module with Reduced Data Block
Page 80 of 223
ProSoft Technology, Inc.
Modbus Memory Map
Based on the configuration described above, below is the default Modbus
address for the module. Each register within the module can be accessed as a
0x bit address, 1x bit address, 3x register address, or 4x register address.
MVI Address
0x
1x
3x
4x
Tag Address
0
0001 to 0016
10001 to 10016
30001
40001
WriteData[0]
1
0017 to 0032
10017 to 10032
30002
40002
WriteData[1]
2
0033 to 0048
10033 to 10048
30003
40003
WriteData[2]
3
0049 to 0064
10049 to 10064
30004
40004
WriteData[3]
4
0065 to 0080
10065 to 10080
30005
40005
WriteData[4]
5
0081 to 0096
10081 to 10096
30006
40006
WriteData[5]
6
0097 to 0112
10097 to 10112
30007
40007
WriteData[6]
7
0113 to 0128
10113 to 10128
30008
40008
WriteData[7]
8
0129 to 0144
10129 to 10144
30009
40009
WriteData[8]
9
0145 to 0160
10145 to 10160
30010
40010
WriteData[9]
10
0161 to 0176
10161 to 10176
30011
40011
WriteData[10]
50
0801 to 0816
10801 to 10816
30051
40051
WriteData[50]
100
1601 to 1616
11601 to 11616
30101
40101
WriteData[100]
200
3201 to 3216
13201 to 13216
30201
40201
WriteData[200]
500
8001 to 8016
18001 to 18016
30501
40501
WriteData[500]
598
9569 to 9584
19569 to 19584
30599
40599
WriteData[598]
599
9585 to 9600
19585 to 19600
30600
40600
WriteData[599]
600 to 999
N/A
N/A
N/A
N/A
Reserved
1000
31001*
41001
ReadData[0]
1001
31002*
41002
ReadData[1]
1002
31003*
41003
ReadData[2]
1003
31004*
41004
ReadData[3]
1004
31005*
41005
ReadData[4]
1005
31006*
41006
ReadData[5]
1006
31007*
41007
ReadData[6]
1007
31008*
41008
ReadData[7]
1008
31009*
41009
ReadData[8]
1009
31010*
41010
ReadData[9]
1010
31011*
41011
ReadData[10]
1050
31051*
41051
ReadData[50]
1100
31101*
41101
ReadData[100]
1200
31201*
41201
ReadData[200]
1500
31501*
41501
ReadData[500]
1598
31599*
41599
ReadData[598]
1599
31600*
41600
ReadData[599]
The above addressing chart will work with many Modbus applications. Values
listed in the ReadData array for 31001 to 31600 are shown with an * beside
them.