MVI56E-MCMR ♦ ControlLogix Platform
Diagnostics and Troubleshooting
Modbus Communication Module with Reduced Data Block
User Manual
ProSoft Technology, Inc.
Page 137 of 223
The port configuration error words have the following definitions:
Bit
Description
Value
0
Type code is not valid. Enter a value from 0 (Master) to 1
(Slave).
0x0001
1
The float flag parameter is not valid.
0x0002
2
The float start parameter is not valid.
0x0004
3
The float offset parameter is not valid.
0x0008
4
Protocol parameter is not valid.
0x0010
5
Baud rate parameter is not valid.
0x0020
6
Parity parameter is not valid.
0x0040
7
Data bits parameter is not valid.
0x0080
8
Stop bits parameter is not valid.
0x0100
9
Slave ID is not valid.
0x0200
10
Input bit or word, output word and/or holding register
offset(s) are not valid.
0x0400
11
Command count parameter is not valid.
0x0800
12
Spare
0x1000
13
Spare
0x2000
14
Spare
0x4000
15
Spare
0x8000
Correct any invalid data in the configuration for proper module operation. When
the configuration contains a valid parameter set, all the bits in the configuration
words will be clear. This does not indicate that the configuration is valid for the
user application. Make sure each parameter is set correctly for the specific
application.
Note: If the APP, BP ACT and OK LEDs blink at a rate of every one-second, this indicates a
serious problem with the module. Call ProSoft Technology Support to arrange for repairs.