Start Here
MVI56E-MCMR ♦ ControlLogix Platform
User Manual
Modbus Communication Module with Reduced Data Block
Page 26 of 223
ProSoft Technology, Inc.
2
Select the
1756-M
ODULE
(G
ENERIC
1756
M
ODULE
)
from the list and click
OK.
This action opens the
N
EW
M
ODULE
dialog box.
3
Set the Module Properties values as follows:
Parameter
Value
Name
Enter a module identification string. The recommended value is
MCMR, as this name will be linked automatically with the MSG
paths, irrespective of the slot location.
Description
Enter a description for the module. Example: ProSoft
communication module for Modbus Serial protocol
communications.
Comm Format
Select
D
ATA
-INT
(*Very Important*)
Slot
Enter the slot number in the rack where the MVI56E-MCMR
module is to be installed.
Input Assembly Instance
1
Input Size
42
Output Assembly Instance
2
Output Size
42
Configuration Assembly Instance 4
Configuration Size
0