MVI46-PDPS ♦ SLC Platform
Diagnostics and Troubleshooting
Profibus DP Slave Communication Module
User Manual
ProSoft Technology, Inc.
Page 24 of 53
Byte 10 Data - Specific Product Code Value
34 = ASCII "4" = MVI46
35 = ASCII "5" = MVI56
36 = ASCII "6" = MVI69
37 = ASCII "7" = MVI71
51 = ASCII "Q" = PTQ
Sample Diagnostics reported to master.
Translated as follows:
Extended diagnostics length
0E= 14 bytes,
Product Version
56 = "V", 30 = "0", 31 =
"1", 2E = ".", 30 = "0", 35 = "5", Product Name 50 = ""P", 44 = ""D", 53 = "S", 34 = "4"
(MVI46),
Status Register [0]
41 = SPC3 in passive idle and WD-State is in DP_Control State,
Status Register [1]
03 = 1.5 Baud rate,
Module State
04 = not in data exchange.