PROFIBUS Slave Error and Status Data
The PROFIBUS Slave Error and Status Data area is discussed in this section. This
information is available in the PDPS status data file, and found in the diagnostic
PROFIBUS SLAVE STATUS screen. See Diagnostics and Troubleshooting (page 23)
for more information.
The data area is initialized with zeros whenever the module is initialized. This occurs
during a cold-start (power-on) or a warm-boot operation. Counter values are also
initialized to 0 at power up.
Word
Value
Description
135
Status
PROFIBUS enable state
136
Status
PDPS module state
137
Status
PROFIBUS status register[0]
138
Status
PROFIBUS status register[1]
139
Status
Diagnostic state
140
Status
PROFIBUS input counter
141
Status
PROFIBUS output counter
142
Status
Reserved
143
Status
Reserved
144
Status
Reserved
145
Status
Reserved
146
Status
Reserved
147
Status
Reserved
148
Status
Last global command
Refer to the following topics to interpret the status/error codes present in the data area.
PROFIBUS Enable State: Word 135
Indicates the initialized state of the PDPS module.
0 = Module is not initialized
1 = Module is initialized
MVI46-PDPS Module State - Word 136
Indicates the current state of the MVI46-PDPS module.
0 = Normal Operation
1 = Shutdown
2 = File Transfer
3 = SPC3 ASIC problem
4 = Not in data exchange