Configuring the MVI69E-MBTCP Using PCB
MVI69E-MBTCP ♦ CompactLogix Platform
User Manual
Modbus TCP/IP Enhanced Communication Module
Page 54 of 150
ProSoft Technology, Inc.
June 28, 2017
register and digital point address assignments.
Note: The value you enter here does not need to include the
"Modbus Prefix" addressing scheme. Also, this value is an offset of
the zero-based Modbus addressing scheme.
Example: When using a Modbus Function Code 3 to read from
address 40010 in the server, enter a value of ‘9’ for this parameter.
The firmware (internally) adds a ‘40001’ offset to the value
entered. This is the same for all Modbus addresses (0x, 1x, 3x,
4x).
Override Value
Upon Error
This parameter is only applicable when the
Enable
parameter is 3
(Bit/Word Override) or 4 (Float Override).
If an error occurs associated with a read command, the module
automatically populates the associated database area with this
override value.