Adding the Module to RSLogix
MVI69E-MBTCP ♦ CompactLogix Platform
User Manual
Modbus TCP/IP Enhanced Communication Module
Page 20 of 150
ProSoft Technology, Inc.
June 28, 2017
2
In the
Module Type Vendor Filters
area, uncheck all boxes except the
P
RO
S
OFT
T
ECHNOLOGY
box. A list of ProSoft Technology modules appears.
3
Select the
MVI69E-MBTCP
module in the list and click
C
REATE
.
4
In the
New Module
dialog box, edit the
N
AME
and
S
LOT
. Click
OK
.
Note : The I/O
T
ABLE
S
IZES
above should reflect the Block Transfer Size parameter set in ProSoft
Configuration Builder (see Module Configuration Parameters (page 47)).
A Block Transfer Size of 60 uses an I/O
T
ABLE
S
IZE
of 62/61 words.
A Block Transfer Size of 120 uses an I/O
T
ABLE
S
IZE
of 122/121 words.
A Block Transfer Size of 240 uses an I/O
T
ABLE
S
IZE
of 242/241 words.