MVI69E-MBTCP ♦ CompactLogix Platform
Adding the Module to RSLogix
Modbus TCP/IP Enhanced Communication Module
User Manual
ProSoft Technology, Inc.
Page 33 of 150
June 28, 2017
6
If the module is not located in the default slot (or is in a remote rack), edit the
connection input and output variables that define the path to the module in
the
F
INAL
N
AME
column (
N
AME
column for RSLogix version 16 or less). For
example, if your module is located in slot 3, change
Local:1:I
in the
F
INAL
N
AME
column to
Local:3:I.
Do the same for
Local:1:O
.
Note: If your module is located in Slot 1 of the local rack, this step is not required.
7
Click
OK
to confirm the import. RSLogix indicates that the import is in
progress:
When the import is completed, the new rung with the Add-On Instruction is
visible as shown in the following image.
The procedure has also imported new user-defined data types, data objects
and the Add-On instruction to be used in the project with the MVI69E-MBTCP
module.