MVI46-PDPMV1 

SLC Platform 

PROFIBUS DPV1 Master 

 

March 25, 2011    

USER MANUAL 

 

Содержание inRAx MVI46-PDPMV1

Страница 1: ...MVI46 PDPMV1 SLC Platform PROFIBUS DPV1 Master March 25 2011 USER MANUAL...

Страница 2: ...User Manual March 25 2011 ProSoft Technology ProLinx inRAx ProTalk and RadioLinx are Registered Trademarks of ProSoft Technology Inc All other brand or product names are or may be trademarks of and a...

Страница 3: ...been switched off or the area is known to be nonhazardous C Suitable for use in Class I division 2 Groups A B C and D Hazardous Locations or Non Hazardous Locations ATEX Warnings and Conditions of Sa...

Страница 4: ...tional 50 g non operational Vibration 5 g from 10 Hz to 150 Hz Relative Humidity 5 to 95 with no condensation All phase conductor sizes must be at least 1 3 mm squared and all earth ground conductors...

Страница 5: ...ng Your PC to the Module 22 2 Configuring the MVI46 PDPMV1 Module 23 2 1 Setting Up the Project 24 2 2 Setting Module Parameters 26 2 2 1 Input Data Size 27 2 2 2 Output Data Size 27 2 2 3 Input Byte...

Страница 6: ...Word 90 4 4 2 Return Codes 91 4 4 3 Error Codes 92 4 4 4 DP V1 Error Codes 93 5 Diagnostics and Troubleshooting 95 5 1 Basic Troubleshooting Steps 96 5 2 LED Status Indicators Front of MVI46 Module 9...

Страница 7: ...Port 144 6 8 Supported PROFIBUS Services 145 6 9 Constructing a Bus Cable for PROFIBUS DP 146 7 Support Service Warranty 151 Contacting Technical Support 151 7 1 Return Material Authorization RMA Pol...

Страница 8: ...Contents MVI46 PDPMV1 SLC Platform User Manual PROFIBUS DPV1 Master Page 8 of 160 ProSoft Technology Inc March 25 2011...

Страница 9: ...system requirements hardware installation and basic configuration Diagnostic and Troubleshooting Diagnostics and Troubleshooting page 95 This section describes Diagnostic and Troubleshooting procedure...

Страница 10: ...Guide to the MVI46 PDPMV1 User Manual MVI46 PDPMV1 SLC Platform User Manual PROFIBUS DPV1 Master Page 10 of 160 ProSoft Technology Inc March 25 2011...

Страница 11: ...Sample Program to the Processor 19 Connecting Your PC to the Module 22 To get the most benefit from this User Manual you should have the following skills Rockwell Automation RSLogix software launch t...

Страница 12: ...module The module requires 800mA of available power Rockwell Automation RSLogix 500 programming software Rockwell Automation RSLinx communication software Pentium II 500 MHz minimum Pentium III 733 MH...

Страница 13: ...ion Important Before beginning the installation please verify that all of the following items are present Qty Part Name Part Number Part Description 1 MVI46 PDPMV1 Module MVI46 PDPMV1 PROFIBUS DPV1 Ma...

Страница 14: ...ccess to the Internet you can install ProSoft Configuration Builder from the ProSoft Solutions Product CD ROM included in the package with your module To install ProSoft Configuration Builder from the...

Страница 15: ...etup pins are not connected and the module s firmware cannot be overwritten Do not jumper the Setup pins together unless you are directed to do so by ProSoft Technical Support The following illustrati...

Страница 16: ...us injury or death to personnel Refer to the documentation for each device you plan to connect to verify that suitable safety procedures are in place before installing or servicing the device After yo...

Страница 17: ...e securely in the locking holes of the rack 5 Make a note of the slot location You will need to identify the slot in which the module is installed in order for the sample program to work correctly Slo...

Страница 18: ...e 18 of 160 ProSoft Technology Inc March 25 2011 1 6 Connecting Your PC to the Processor 1 Connect the right angle connector end of the cable to your controller at the communications port 2 Connect th...

Страница 19: ...essor open the COMMUNICATIONS menu and then choose DOWNLOAD RSLogix will establish communication with the processor 2 Click the DOWNLOAD button to transfer the sample program to the processor 3 RSLogi...

Страница 20: ...communication with the processor follow these steps 1 Open RSLinx 2 Open the COMMUNICATIONS menu and choose CONFIGURE DRIVERS This action opens the Configure Drivers dialog box Note If the list of co...

Страница 21: ...inx will attempt to configure your serial port to work with the selected driver 5 When you see the message Auto Configuration Successful click the OK button to dismiss the dialog box Note If the auto...

Страница 22: ...nnect your PC to the Configuration Debug port using the RJ45 DB 9 Serial Adapter Cable and the Null Modem Cable included in the package with the MVI46 PDPMV1 module 1 Connect the RJ45 DB 9 Serial Adap...

Страница 23: ...Verifying Correct Operation 50 Because the task of configuring the PROFIBUS network can be challenging ProSoft Technology has provided a configuration tool called ProSoft Configuration Builder PCB th...

Страница 24: ...s of a tree view on the left and an information pane and configuration pane on the right side of the window When you first start ProSoft Configuration Builder the tree view consists of folders for Def...

Страница 25: ...hortcut menu select CHOOSE MODULE TYPE This action opens the Choose Module Type dialog box 3 In the Product Line Filter area of the dialog box select MVI46 In the Select Module Type dropdown list sele...

Страница 26: ...e following steps you will provide the missing information to begin configuring the module 1 Click the plus sign next to the module icon to expand the module tree and then expand the MVI PDPM V1 tree...

Страница 27: ...ime you may wish to rename the Default Project and Default Location folders in the tree view To rename an object 1 Select the object and then click the right mouse button to open a shortcut menu From...

Страница 28: ...being stored in memory Example With Input Byte Swap set to NO incoming order is unchanged ABCDEF With Input Byte Swap set to YES each byte pair is swapped BADCFE 2 2 4 Output Byte Swap YES or NO This...

Страница 29: ...the MVI46 module You will also export the I O maps for the processor 1 In PCB tree view click to expand the MVI46 PDPMV1 tree and then double click the PROFIBUS DP icon This action opens the PDPMV1 PR...

Страница 30: ...iguration information about the PROFIBUS slaves you add to the network The GSD configuration files identify the slave s capabilities so that the MVI46 PDPMV1 can communicate with it correctly Slave de...

Страница 31: ...t allows you to browse for the location of the GSD configuration files to install Depending on the device and language used in the file the actual extension may be GSD GSE GSS or other combinations he...

Страница 32: ...a ProLinx PROFIBUS slave module The configuration information GSD file for this module is provided on the MVI46 PDPMV1 Solutions CD ROM 1 In ProSoft Configuration Builder for PROFIBUS click the plus...

Страница 33: ...the plus sign to expand the slave device you added This action opens a list of device configuration values The following illustration shows the device configuration values for a ProLinx PROFIBUS slav...

Страница 34: ...f 160 ProSoft Technology Inc March 25 2011 5 Drag the input and output parameters to the slot location grid below the Bus Configuration window This view displays the configuration data order number an...

Страница 35: ...through 6 for all slaves you intend to place on the network 8 When you are finished adding slaves open the Project menu and choose EXIT to return to the Master Setup dialog box Using The Autoscan Feat...

Страница 36: ...initialize the Master even if the database does not contain any slaves After successful initialization the PROFIBUS Master Configuration window will issue the following mailboxes in order to gather in...

Страница 37: ...FIBUS DPV1 Master User Manual ProSoft Technology Inc Page 37 of 160 March 25 2011 When the information is collected the PROFIBUS Master Configuration window will find a matching GSD file and extract i...

Страница 38: ...first module found Example If a slave responds with identifier bytes 0x11 0x21 0x31 and that the associated GSD file contains five modules A 0x11 B 0x21 C 0x31 AB 0x11 0x21 and BC 0x21 0x31 The PROFI...

Страница 39: ...ible for the user to adopt the slave to the configuration since it is not allowed to exchange data with devices having this address The check box in the Select column will be grayed out To be able to...

Страница 40: ...h 25 2011 Example After scanning the network finds these other slaves 2 6 25 and 40 Slaves 2 6 and 25 are found but are marked as in the bus configuration the mapping of the inputs and outputs will no...

Страница 41: ...ill update the Network scan window as shown here The node address will be updated to the one that the user selected in the Set Slave dialog box Slave In this column the name of the slave as stated in...

Страница 42: ...r bytes as the first matching module will be displayed in the drop down list GSD file This column shows the name of the GSD file that matches the Ident number derived from the SlaveDiag mailbox messag...

Страница 43: ...ave accordingly Rescan Pressing the YES button will trigger a new network scan Before proceeding with the scan a message similar to the one below will appear If a new scan is accepted detected slaves...

Страница 44: ...ose and the PROFIBUS Master Configuration window will be populated with the slaves that were found during the network scan Note Slave is equal to the Ident number and that the Device path and Order nu...

Страница 45: ...tion file was imported to the processor Any change to the contents of the configuration file in either location changes the unique numeric CRC value for the file If the checksum values do not match th...

Страница 46: ...orrespond to the input and output data you configured for the PROFIBUS slaves page 31 Notice also that there are check boxes to display slot numbers and PROFIBUS addresses 3 Click PRINT to print the i...

Страница 47: ...ft Configuration Builder click once to select the module 2 Right click the module icon to open a shortcut menu From the shortcut menu choose DOWNLOAD FROM PC TO DEVICE The program will scan your PC fo...

Страница 48: ...se the XML file created by ProSoft Configuration Builder in this step to simplify the task of configuring additional PROFIBUS network modules Because it saves the entire network configuration you can...

Страница 49: ...older with the same name as the name you used to save your PCB configuration ppf file When you exit PCB you will be prompted to overwrite your Export folder files If you have made changes to your conf...

Страница 50: ...ble to connect to the processor using RSLogix 500 View the Data Files in RSLogix 500 page 56 If you are able to connect to the processor using RSLogix 500 Send a Mailbox Message in RSLogix 500 page 58...

Страница 51: ...der will establish communication with the MVI46 PDPMV1 module and will indicate communication status o If the slave icon in the Bus Configuration window has a green border then the MVI46 PDPMV1 module...

Страница 52: ...Soft Technology Inc March 25 2011 2 In the Online Slave Properties dialog box click the DIAGNOSTIC tab and select CHECK DETAILS FOR SLAVE DIAGNOSTIC Slave diagnostic information will appear in the Dia...

Страница 53: ...ion State If the Master and the slave are communicating correctly the operation state will be C0 hex 5 Note the values in SLAVE CFG LIST TRANSFER LIST and SLAVE DIAG LIST If the Master and slave are c...

Страница 54: ...uping represents one word containing 16 slave addresses In SLAVE CFG LIST in the example above To find out which slave addresses in Word 1 are occupied by configured slaves expand Word 1 s hexadecimal...

Страница 55: ...aves are actually communicating with the Master Notice that Word 1 is different in the TRANSFER LIST Here is the bitmap for Word 1 in the TRANSFER LIST In conclusion there are configured slaves at add...

Страница 56: ...n your PC to the DB9M connector on the SLC processor 1 Open the sample ladder logic in RSLogix 500 2 Open the COMMUNICATIONS menu and choose GO ONLINE 3 In the Project Browser window double click N11...

Страница 57: ...ou can add ladder logic to perform an action based on the values of these tags for example to determine if a slave is misconfigured If the values of these tags show that the slave is configured but is...

Страница 58: ...2 Open the COMMUNICATIONS menu and choose GO ONLINE 3 In the Project Browser window double click the B3 Data File 4 Enter 1 number one in B3 0 4 5 Next double click on N51 and read the response to ve...

Страница 59: ...asks that must be handled by the ladder logic are module data transfer special block handling and status data receipt Additionally a power up handler may be needed to handle the initialization of the...

Страница 60: ...1 Add the MVI46 PDPMV1 module to the project Double click I O CONFIGURATION in the Controller Organization window 2 This action opens the I O Configuration dialog box Select an empty slot in the left...

Страница 61: ...t the module you selected is now in the list in the left pane of the I O Configuration dialog box 6 Select and double click the new module in the left pane This action opens the Advanced I O Configura...

Страница 62: ...them into your existing program Important Take care not to overwrite existing data files in your application with data files in the sample application Rename either the source or the destination data...

Страница 63: ...Data Telegrams and Acyclic Data Telegrams Cyclic data communication is the exchange of normal slave input and output I O data and is handled automatically by the Master in a defined recurring determi...

Страница 64: ...ription Output message from processor 126 Number of messages that the MVI46 module will queue by type of message Note that status of the queues can be monitored via the Queue Message Count values Inpu...

Страница 65: ...et Slave Config Gets slave configuration Set Slave Address Sets node address of a slave if supported by the slave Get Live List Gets information from all nodes on the network MSAC1 Read DPV1 acyclic r...

Страница 66: ...ommands 149 4 2 1 Mailbox Message Set Slave Mode In addition to station related user data transfer which is executed automatically the Master can send control commands to a single slave a group of sla...

Страница 67: ...nded Header Data Fault information may be returned in the header of the response Command and Response Layout Set Slave Mode Command Response Message ID ID ID Message information 4002h 0002h Command 00...

Страница 68: ...D0h If an individual slave should be addressed the correct group selection must also be made because the slave will ignore the message if it does not belong to the requested group s What group s a sl...

Страница 69: ...be Freeze Group 0250h Invalid Sync Group Group is not initiated to be Sync Group 0350h Incorrect Control Command 0450h No Sync or Freeze groups enabled in Master configuration FE00h Command not possi...

Страница 70: ...et low 0000h 0000h Extended word 1 Slave Address Type of Request Slave Address Type of Request Extended word 2 Extended word 3 Extended word 4 Extended word 5 Extended word 6 Extended word 7 Extended...

Страница 71: ...des page 90 Return Code Refer to Mailbox Messaging Error Codes page 90 Fault Information If Invalid Other is returned in the Message Information word in the header of the response information about th...

Страница 72: ...of the response Command and Response Layout Get Slave Configuration Command Response Message ID ID ID Acyclic Message Status Word 4002h 0002h Command 0005h 0005h Get Slave Configuration Data size 000...

Страница 73: ...ault can be found here Refer to Acyclic Message Status Word page 90 0100h Address out of range 0A00h Failed to execute request Refer to Return Codes page 91 for additional information 0B00h Remote sta...

Страница 74: ...s Current Slave Addr New Slave Address Extended word 2 Slave Ident Number Slave Ident Number Extended word 3 No_add_ Chg No_add_ Chg Extended word 4 Extended word 5 Error Code 1 Error Code 2 Extended...

Страница 75: ...efault address 126 Error Code 1 4 If Return Code equals 3080h Negative indication from lower layer status values according to the DP specification in available in Error Code 1 Error Codes 2 and 3 are...

Страница 76: ...mand Number 1800h Fragmented No Extended Header Data Fault information may be returned in the header of the response Command and Response Layout Get Live List Command Response Message ID ID ID Message...

Страница 77: ...ion 04h Station does not exist Fault Information If Invalid Other is returned in the Message Information word in the header of the response information about the fault can be found here Refer to Messa...

Страница 78: ...low 0000h 0000h Extended word 1 Slave Addr Slot Number Slave Addr Slot Number Extended word 2 Index Length Index Length Extended word 3 Extended word 4 Extended word 5 Error Decode Extended word 6 Err...

Страница 79: ...Fault Information Contents 0100h Address out of range 0A00h Failed to execute request Refer to Return Codes page 91 0B00h Remote station failure 1000h Remote station DPV1 failure Function_Number 1100...

Страница 80: ...set high 0000h 0000h Offset low 0000h 0000h Extended word 1 Slave Addr Slot Number Slave Addr Slot Number Extended word 2 Index Length Index Length Extended word 3 Extended word 4 Extended word 5 Erro...

Страница 81: ...here Fault Information Extended Fault Information Contents 0100h Address out of range 0A00h Failed to execute request Refer to Return Codes page 91 0B00h Remote station failure 1000h Remote station DP...

Страница 82: ...00h 0000h Offset low 0000h 0000h Extended word 1 Slave Address Slot Number Extended word 2 Seq Number Alarm Spec Ack Extended word 3 Alarm Type Ext Diag Extended word 4 Extended word 5 Extended word 6...

Страница 83: ...Data 1 n Additional manufacturer specific alarm information Alarm PDU Fault Information If the Message Information word in the header of the message indicates Invalid Other addition information is ava...

Страница 84: ...eq Mode Conf Req Extended word 2 Extended word 3 Extended word 4 Extended word 5 Extended word 6 Extended word 7 Extended word 8 Fault Information Mode 40h STOP 80h CLEAR C0h OPERATE Conf Req 00h Conf...

Страница 85: ...application can find out about this situation by evaluating the Fault information and Message data words of the response Command and Response Layout Start Slave Command Response Message ID ID ID Messa...

Страница 86: ...xtended word 7 If Extended word 8 equals 0x000A Failed to execute request additional info can be found here Fault information Extended word 8 0x0001 Invalid setting in Message data word 1 63 of the co...

Страница 87: ...ation by evaluating the Fault information and Message data words of the response Command and Response Layout Stop Slave Command Response Message ID ID ID Message information 4002h 0002h Command 000Ch...

Страница 88: ...Extended word 8 equals 0x000A Failed to execute request additional info can be found here Fault information Extended word 8 0x0001 Invalid setting in Message data word 1 63 of the command 0x0002 At l...

Страница 89: ...lbox Message ID processed from Output Image 77 Current In Mailbox Control Index 78 Current Alarm Control Index 79 to 222 Incoming Mailbox Message data 223 to n PROFIBUS Input Data The important sectio...

Страница 90: ...any errors 0 1 Message OK Error See also Error Code below C R This bit specifies whether the message is a command or a response 0 1 Response Message Command Message Error Code If the ERR bit is set t...

Страница 91: ...MC_ERR_V1C_L2_REQ Unknown opcode in the confirmation 8026h DPMC_ERR_V1C_TIMEOUT Active request terminated with timeout 8028h DPMC_ERR_V1C_INVALID_LEN Invalid length in user request 8030h DPMC_ERR_V1C_...

Страница 92: ...ndicates DPMC_ERR_V1C_REQ_NEG the status values according to the DP standard may be available in Error Code 1 Refer to the PROFIBUS DP specification for information on how to interpret these status va...

Страница 93: ...red an undefined state 002Fh DPMC_ERR_M_SLAVE_NOT_FOUND Slave does not respond 0031h DPMC_ERR_M_TIMEOUT Active request terminated with timeout 0034h DPMC_ERR_M_INVALID_LEN Invalid length in user reque...

Страница 94: ...Mailbox Messaging MVI46 PDPMV1 SLC Platform User Manual PROFIBUS DPV1 Master Page 94 of 160 ProSoft Technology Inc March 25 2011...

Страница 95: ...PCB for Diagnostics 102 Standard PROFIBUS Slave Diagnostic Bytes 108 The module provides information on diagnostics and troubleshooting in the following forms LED status indicators on the front of the...

Страница 96: ...5 2011 5 1 Basic Troubleshooting Steps 1 Verify that the module is installed correctly and is communicating with the processor 2 Install the most current version of ProSoft Configuration Builder 3 Not...

Страница 97: ...c Page 97 of 160 March 25 2011 5 2 LED Status Indicators Front of MVI46 Module The LEDs indicate the module s operating status The module has two sets of LED status indicators MVI46 Module Status LEDs...

Страница 98: ...le is able to communicate over the backplane OFF The LED is OFF when the module is unable to communicate with the processor The processor is either absent or not running BATT Red OFF The battery volta...

Страница 99: ...ine GREEN Flashing Database download in progress GREEN 1 second RED 2 seconds Module in Legacy mode while the Flex ladder is loaded to the processor Check processor program RED Invalid database OFF No...

Страница 100: ...inking DBASE STAT GREEN PROFIBUS has been configured TKN HOLD GREEN MVI is holding the PROFIBUS token MSTR STAT GREEN Master is in operate mode MVI46 PDPMV1 module does not see the processor RUN ON or...

Страница 101: ...25 2011 Processor Status MVI46 PDPMV1 Module Status PROFIBUS Master Status PROFIBUS Master Status LED Description CPU is stopped STOP ACTIVE COM STAT OFF Master is not communicating with configured sl...

Страница 102: ...mmands by typing the command letter from your computer keyboard in the Diagnostic window in ProSoft Configuration Builder PCB The module does not respond to mouse movements or clicks The command execu...

Страница 103: ...OFIBUS DPV1 Master User Manual ProSoft Technology Inc Page 103 of 160 March 25 2011 2 On the shortcut menu choose DIAGNOSTICS This action opens the Diagnostics dialog box 3 Press to open the Main menu...

Страница 104: ...than one serial port verify that your communication program is connected to the same port that is connected to the module If you are still not able to establish a connection contact ProSoft Technology...

Страница 105: ...om your computer your terminal screen will be blank To activate the main menu press the key on your computer s keyboard If the module is connected properly the following menu will appear Caution Some...

Страница 106: ...odule Configuration screen Use this command to display the current configuration and statistics for the module Viewing Version Information Press V to view version information for the module Use this c...

Страница 107: ...ion state where 00 Offline 40 Stop 80 Clear C0 Operate Viewing Control Registers Press 3 to view information about the PROFIBUS Master s Control Registers Use this command to view general information...

Страница 108: ...in the tables below Byte Description 0 Station status 1 1 Station status 2 2 Station status 3 3 Master address 4 Ident number high 5 Ident number low 5 6 1 Byte 0 Station Status 1 Bits Bit Description...

Страница 109: ...6 4 Byte 3 Master Address This byte shows the address of the assigned PROFIBUS Master after parameterization If there is an error during the parameterization process this byte will display the value F...

Страница 110: ...Diagnostics and Troubleshooting MVI46 PDPMV1 SLC Platform User Manual PROFIBUS DPV1 Master Page 110 of 160 ProSoft Technology Inc March 25 2011...

Страница 111: ...eference In This Chapter Product Specifications 112 Functional Overview 114 PROFIBUS comDTM 122 Disabling the RSLinx Driver for the Com Port on the PC 140 RS 232 Configuration Debug Port 142 DB9 to RJ...

Страница 112: ...rom the processor is asynchronous with the I O data transfer on the PROFIBUS network 6 1 1 General Specifications Single slot 1746 backplane compatible local or extended I O rack only remote rack not...

Страница 113: ...data DPV1 Multiple Masters can be placed in a single rack CRC checksum determination of slave configuration consistency to processor Master Status LED indicators for Operations Network Communication M...

Страница 114: ...989 PROFIBUS is a Master slave protocol The Master establishes a connection to one or more remote slaves When the connection is established the Master sends the PROFIBUS poll messages called telegrams...

Страница 115: ...program extracts the data and places it in the module s internal database To read data from the module use the COP instruction to copy data from the processor s M1 file to a user data file To write d...

Страница 116: ...etwork the MVI46 PDPMV1 module and the SLC processor M1 Input Image Input Data Area Map M1 File M1 Word Offset Description 0 to 12 Configuration Data 13 to 78 Status Control Data 79 to 222 In Mailbox...

Страница 117: ...word High byte User configured flag to indicate if output data is byte swapped in each word after receiving from the output image of the controller If 0 no swapping If not 0 then swap bytes in each w...

Страница 118: ...byte MSB High byte Least significant byte LSB Example for Version 1 40 High Byte 0x40 Low Byte 0x01 42 PROFIBUS Master module s operating status Low byte Most significant byte MSB High byte Least sign...

Страница 119: ...unter Number of acyclic read request messages processed by the module 55 Module acyclic write request message counter Number of acyclic write request messages processed by the module 56 Module backpla...

Страница 120: ...he PROFIBUS Cyclic Input data received from the slave or slaves M0 Output Image Output Data Area Map M0 File M0 Word Offset Description 0 Last in mailbox control index 1 Last alarm control index 2 to...

Страница 121: ...organize this communication 6 2 4 Communication Types In addition to point to point data transfer the PROFIBUS protocol can also handle the following types of communication Broadcast communication An...

Страница 122: ...tools instruments and communication devices on a field network to recognize and use the module s capabilities Communication Channels Supported Serial Ethernet Product Local RS 232 Port Local Ethernet...

Страница 123: ...the software environment of either the device or the host system FDT allows any device to be accessed from any host through any protocol The FDT container implements the FDT specification It serves as...

Страница 124: ...cation DTM comDTM for each supported fieldbus protocol This ensures that the details of the PC network interface cards and pass through protocols of the host system are transparent to the device vendo...

Страница 125: ...What is PROFIBUS PROFIBUS Process Field Bus is a widely used open standards protocol created by a consortium of European factory automation suppliers in 1989 PROFIBUS is a Master slave protocol The M...

Страница 126: ...port since many Ethernet to serial converters require the configuration of a fixed UDP port which is not available for the current implementation Note for MVI56 PDPMV1 users The Ethernet connection u...

Страница 127: ...ndows Explorer file tree window 3 Double click to open the UTILITIES folder then navigate to COMDTM COMDTM INSTALL 4 Double click the SETUP EXE file This action starts the installation wizard 5 Follow...

Страница 128: ...FDT program and login as administrator The following procedures use PACTware 3 0 software 2 Click the UPDATE DEVICE CATALOG button If PROFIBUS comDTM was installed successfully it will appear in the...

Страница 129: ...u used when setting up the device Connecting the comDTM to the Master to Establish Communication Note The features described in this section require the current version of PROFIBUS comDTM You can alwa...

Страница 130: ...1 2 If you have not created a communication path click the ADD button If you have already created a path skip to step 5 3 For PTQ PDPMV1 and ProLinx PDPMV1 users Select the ETHERNET tab and enter the...

Страница 131: ...number on your PC connected to the module Enter a descriptive path name For MVI56 PDPMV1 and MVI69 PDPMV1 users with CIPconnect Select the CIPCONNECT tab and then click the ADD button Click the CIPCO...

Страница 132: ...ted in slot 3 of the same rack For more information please refer to Using the CIPconnect Path Editor Note CIPconnect is available for MVI56 PDPMV1 firmware version 1 28 000 or later and for MVI69 PDPM...

Страница 133: ...The communication path will be displayed at the top grid panel as shown in the following illustration 5 Select the path and click the OK button to exit the Transport Path Editor window 6 Select the CO...

Страница 134: ...p and documentation additional information on each DTM component you have installed and configured The comDTM provides a Guided Tour section in the online help that explains the basic features and ope...

Страница 135: ...versions associated to the comDTM the comDTM version and the comDTM install version Starting with comDTM version 1 0 1 5 each upgrade will indicate the same comDTM version but a different comDTM insta...

Страница 136: ...Manual PROFIBUS DPV1 Master Page 136 of 160 ProSoft Technology Inc March 25 2011 Checking the comDTM Install Version 1 Click the START menu and then choose CONTROL PANEL 2 In the list of CONTROL PANE...

Страница 137: ...60 March 25 2011 3 Select PROSOFT TECHNOLOGY COM DTM and then click on the link CLICK HERE FOR SUPPORT INFORMATION 4 You will see the comDTM Install Version in the Version field as shown in the follow...

Страница 138: ...Reference MVI46 PDPMV1 SLC Platform User Manual PROFIBUS DPV1 Master Page 138 of 160 ProSoft Technology Inc March 25 2011 2 Select UNINSTALL PROGRAMS 3 Select Prosoft Technology COM DTM click once...

Страница 139: ...m Reference PROFIBUS DPV1 Master User Manual ProSoft Technology Inc Page 139 of 160 March 25 2011 4 Click the ORGANIZE tab and select LAYOUT DETAILS PANE 5 Check the Install Version at the bottom righ...

Страница 140: ...minal emulator follow these steps to disable the RSLinx driver 1 Open RSLinx and go to COMMUNICATIONS RSWHO 2 Make sure that you are not actively browsing using the driver that you wish to stop The fo...

Страница 141: ...the STOP button on the side of the window 5 After you have stopped the driver you will see the following 6 You may now use the com port to connect to the debug port of the module Note You may need to...

Страница 142: ...guration Debug Port This port is physically an RJ45 connection An RJ45 to DB 9 adapter cable is included with the module This port permits a PC based terminal emulation program to view configuration a...

Страница 143: ...MVI46 PDPMV1 SLC Platform Reference PROFIBUS DPV1 Master User Manual ProSoft Technology Inc Page 143 of 160 March 25 2011 6 6 DB9 to RJ45 Adaptor Cable 14...

Страница 144: ...PROFIBUS DPV1 Master Page 144 of 160 ProSoft Technology Inc March 25 2011 6 7 PROFIBUS Master Port The following diagram has been imported from the PROFIBUS Master documentation Note that the signals...

Страница 145: ...No DDLM_Global_Control DP V0 Yes No DDLM_Get_Cfg DP V0 Yes DDLM_Set_Slave_Add DP V0 Yes DDLM_Read_Input DP V0 No DDLM_Read_Output DP V0 No DDLM_Get_Master_Diag DP V0 Yes DDLM_Start_Seq DP V0 No No DD...

Страница 146: ...r convenience PROFIBUS connector Siemens part number 6ES7972 0BA40 0XA0 PROFIBUS cable Belden part number 3079A To construct the cable proceed as follows 1 Cut the cable to the required length 2 Prepa...

Страница 147: ...for reliving tension E Bus connector screws 6 Attach the cables with the provided cable cleat to create a robust shielded connection and to relieve any tension as shown J PVC Jacket S Braided shieldi...

Страница 148: ...e end of the bus These connectors emulate the line impedance It is recommended that at least one connector with diagnostics interface is used Wiring diagram for a PROFIBUS DP cable Grounding and Shiel...

Страница 149: ...ng Grounding and Shielding for Systems without Equipotential Bonding Note Grounding and shielding is to be carried out the same as for systems with equipotential bonding If this is not possible becaus...

Страница 150: ...Reference MVI46 PDPMV1 SLC Platform User Manual PROFIBUS DPV1 Master Page 150 of 160 ProSoft Technology Inc March 25 2011...

Страница 151: ...editing this process 1 Product Version Number 2 System architecture 3 Network details If the issue is hardware related we will also need information regarding 1 Module configuration and associated lad...

Страница 152: ...5 34 36 87 20 E mail support EMEA prosoft technology com Languages spoken include French English Europe location in Dubai UAE Tel 971 4 214 6911 E mail mea prosoft technology com Languages spoken inc...

Страница 153: ...Technical Support Engineer will request that you perform several tests in an attempt to isolate the problem If after completing these tests the Product is found to be the source of the problem we wil...

Страница 154: ...is customer generated and is repairable customer can authorize ProSoft Technology to repair the unit by providing a purchase order for 30 of the current list price plus freight charges duties and tax...

Страница 155: ...hased on or after January 1st 2008 or one 1 year from the date of shipment for Product purchased before January 1st 2008 the Warranty Period If the Customer discovers within the Warranty Period a fail...

Страница 156: ...plication neglect or misuse by the Customer vii accident improper testing or causes external to the Product such as but not limited to exposure to extremes of temperature or humidity power failure or...

Страница 157: ...fication without notice c Transfer of title shall not operate to convey to Customer any right to make or have made any Product supplied by ProSoft d Customer is granted no right or license to use any...

Страница 158: ...derstood to be the complete and exclusive agreement between the parties suspending all oral or written prior agreements and all other communications between the parties relating to the subject matter...

Страница 159: ...able for PROFIBUS DP 146 Contacting Technical Support 151 153 Controlling Law and Severability 158 D DB9 to RJ45 Adaptor Cable 14 143 Diagnostics and Troubleshooting 9 95 Disabling the RSLinx Driver f...

Страница 160: ...s Under Warranty 154 RS 232 Configuration Debug Port 142 S Scanning for Slaves Manually 32 Sending a Mailbox Message in RSLogix 500 50 58 Setting Jumpers 15 Setting Module Parameters 23 26 Setting Up...