ILX69-PBM ♦ CompactLogix™ or MicroLogix™ Platform
Communication
PROFIBUS Master Communication Module
User Manual
ProSoft Technology, Inc.
Page 85 of 113
15 hex
0000 hex
Configuration data size
too large
Too much data
transferred with the
CIP Message
Check if the overall length of
the requested command of
the CIP message and the
consistency of all length
parameters within the
requested command.
16 hex
0000 hex
Object not supported
The requested object
does not exist within
the module.
FE hex
0000 hex
Message Timeout
No answer message
was received.
FF hex
0514 hex
General Error
Non specified error
occurred
Contact technical support
FF hex
0517 hex
General Error
Unknown command
The value in the
requested command is
unknown
The value in requested
command must be initialized
Slave Diagnostic
Code
Significance
Error source
Help
0
No error detected
N/A
N/A
17
No response from
the station
Slave
Check network wiring, check bus address of
slave or baud rate support
18
Master not into the
logical token ring
Network in general
Check ILX69-PBM address or highest-station-
address of the master. Examine bus wiring for
bus short circuits.
161
Remote address in
request service out
of range
Host
Check parameter in request message
Set Slave Control
The Global Control command initiates a multicast command on the PROFIBUS network
to all configured slaves. This command is always assumed to be successfully executed
and no error will be placed in
Cnf.Failure
of the response message.
Code
Significance
Error source
Help
0
No error detected
N/A