Communication
ILX69-PBM ♦ CompactLogix™ or MicroLogix™ Platform
User Manual
PROFIBUS Master Communication Module
Page 70 of 113
ProSoft Technology, Inc.
Slave Diag Failure
This byte reflects the status of the Slave Diagnostics request.
Error
Code
Significance
Error
source
Description
0
Service could be executed
without an error
No error
No error detected.
17
No response from the
station
Slave
Check network wiring, bus address of slave, or baud rate
support.
18
Master not in the logical
token ring
Network in
general
Check master DP address or highest-station address of the
master. Examine bus wiring for short circuits.
161
Remote Address in
request service is out of
range
Application Check address parameter in diagnostics request.
Station Status_1
Slave device status information.
Bit
Offset
Member
Name
Data
Type
Description
0
Sta_Non_Exist
BOOL
No response from slave device. The slave is non-existent.
1
Sta_Not_Ready
BOOL
Slave is not ready
2
Cfg_Fault
BOOL
Slave has incorrect parameterization
3
Ext_Diag
BOOL
The extended diagnostics area is used
4
Not_Supp
BOOL
Unknown command is detected by the slave
5
Inv_Slv_Res
BOOL
Invalid slave response
6
Prm_Fault
BOOL
Last parameterization telegram was faulty
7
Master_Lock
BOOL
Slave is controlled by another master
Station Status_2
Slave device status information (continued)
Bit
Offset
Member
Name
Data
Type
Description
0
Prm_Req
BOOL
Parameter Request: Slave must be parameterized
1
Stat_Diag
BOOL
This bit remains active until all diagnostics data has been
retrieved from the slave
2
Slave_Device
BOOL
This bit is always set by the slave
3
WD_On
BOOL
Slave watchdog is activated
4
Freeze_Mode
BOOL
Freeze command active
5
Sync_Mode
BOOL
Sync command active
6
Reserved
BOOL
Reserved, set to 0
7
Deactivated
BOOL
Slave not active