5.6.5 STARTUP.INI File
The STARTUP.INI file contains the following:
1 [Global]
2 Notify=10
3 Restore=always
4 RestorePoint=SDMMC:/backup
Notify=10:
The value for ‘Notify’ is ‘10’. It takes 10 seconds to copy the files from the SD
memory card to the internal flash of the ILX69-PBM.
Restore=always:
The second stage bootloader copies the files in any case.
RestorePoint=SDMMC:/backup:
All data stored under the backup folder is copied to
the SD memory card.
Note:
The STARTUPINI file is automatically created if ‘Store’ and
are used. The user does not need to create this file.
5.6.6 Reset Device to Factory Settings with Memory Card
Using a memory card that has the basic firmware stored on it, the ILX69-PBM can be
restored back to factory settings.
1
Copy the STARTUP.INI file and the backup directory (including all subdirectories)
from the ILX69-PBM webpage at
of an empty memory card.
2
Prepare the memory card and reset the module to the factory settings as described
in section Project File Backup and SD Card Handling (page 55).