MVI69E-MBS ♦ CompactLogix™ Platform
Diagnostics and Troubleshooting
Modbus Serial Enhanced Communication Module
User Manual
ProSoft Technology, Inc.
Page 98 of 159
7
Diagnostics and Troubleshooting
The MVI69E-MBS provides information on diagnostics and troubleshooting in the
following forms:
LED status indicators on the front of the module provide general information on the
module's status.
You can view status data contained in the module through the Ethernet port, using
the troubleshooting and diagnostic capabilities of
ProSoft Configuration Builder
(PCB)
.
You can transfer status data values from the module to processor memory and can
monitor them in the processor manually or by customer-created logic.
7.1
LED Status Indicators
The LEDs indicate the module’s operating status.
LED
Status
Indication
ETH
On
Ethernet communications are ok
Off
No Ethernet cable connected
P1
Green
Data is being transferred between the module and the Modbus
network on Port 1
Red
Communication error detected
Off
No Modbus network activity detected
P2
Green
Data is being transferred between the module and the Modbus
network on Port 2
Red
Communication error detected
Off
No Modbus network activity detected
CFG
Green
Configuration is ok
Yellow
Module is reading configuration
Red
Error setting up Modbus protocol driver, failed startup, or module
shutting down
Off
Processor is in Program mode
BP
Green
The LED is on when the module is performing a write operation on
the backplane. Under normal operation, the LED should blink
rapidly on and off.
Red
Major fault or module shutting down
OK
Green
Module is ok
Red
The program has detected an error or is being configured. If the
LED remains red for over 10 seconds, the program has probably
halted.