MVI69E-MBS ♦ CompactLogix™ Platform
Configuring the Module in RSLogix
Modbus Serial Enhanced Communication Module
User Manual
ProSoft Technology, Inc.
Page 28 of 159
6
If the module is not located in the default slot (or is in a remote rack), edit the
connection input and output variables that define the path to the module in the
F
INAL
N
AME
column (
N
AME
column for RSLogix version 16 or less). For example, if your
module is located in slot 3, change
Local:1:I
in the
F
INAL
N
AME
column to
Local:3:I.
Do the same for
Local:1:O
.
Note: If your module is located in Slot 1 of the local rack, this step is not required.
7
Click
OK
to confirm the import.
8
When the import is completed, the new rung with the Add-On Instruction is visible.
The procedure also imports new user-defined data types, data objects and the Add-
On instruction to be used in the project with the MVI69E-MBS module.