MVI69E-MBS ♦ CompactLogix™ Platform
Configuring the MVI69E-MBS Using PCB
Modbus Serial Enhanced Communication Module
User Manual
ProSoft Technology, Inc.
Page 47 of 159
Example:
Using a Modbus Function Code 3 to read from
address 40010 in the slave, a valu
e of ‘9’ would be entered in
this parameter. The firmware (internally) adds a ‘40001’ offset
to the value entered. This is the same for all Modbus
addresses (0x, 1x, 3x, 4x).
Override Value
Upon Error
This parameter is only applicable for
Enable Codes
3
(Bit/Word Override) or 4 (Float Override).
If an error occurs associated to a read command the module
automatically populates the associated database area with
this override value.
3.2.4 Ethernet 1
This section defines the permanent IP address, Subnet Mask, and Gateway of the
module.
In the ProSoft Configuration Builder tree view, double-click the
E
THERNET
1
icon.
Parameter
Description
IP Address
Unique IP address assigned to the module
Netmask
Subnet mask of module
Gateway
Gateway (if used)