If the alarm stops and the reason for the alarm is identified and resolved (e.g. a kitchen burner lit off
but in the open position) the gas supply may be re-opened after checking that all the gas appliances
are off.
8.
FAULT CODES
PPS panel will display the fault code when an fault condition detected. Press up and down arrow
buttons to see fault codes while fault status raised and fault LED activated:
Here the code details that can help to understand problem and find a resolution:
Fault
Code
Details
10
EFuse Dedektor Power Line Fault
11
No detector installed on zone module
12
Detector in fault status. Either detector raising a fault status or communication to detector
interrupted
13
CO gas selected for detectors but there is no CO detector installed on zone module
14
NO2 gas selected for detectors but there is no NO2 detector installed on zone module
15
LPG gas selected for detectors but there is no LPG detector installed on zone module
Table 8. Fault codes and details
Error 12