17
PRS-UM-PPSM-EN-Rev.03-10.04.2020
Press menu button again to start adjustment. It will ask the gas type :
Gas type can be changed via pressing up and down arrow buttons. There are three gas type
supported by PPS Manager which are CO, NO2, LPG. Once decided press Menu button to continue. It
will show the current level:
Alarm level can be increased or decreased via pressing up and down arrow buttons. For CO gas levels
will increase or decrease by steps 10PPM while for NO2 1PPM and for LPG 1LEL steps. Once the level
set use T button to return back to main menu or press again to exit from menu. FAN1 level cannot be
adjusted higher than the FAN2 relay level or Alarm relay alarm level. Thus user should adjust first the
FAN2 level or Alarm level.
6.2 Set FAN2 Relay Level:
To set alarm level for FAN2 press menu button to see menu items. The second item on menu is “Set
Ext2 “ to set level for FAN2. Thus up and down arrow buttons should be used to reach to “Set Ext2 “
menu item:
Press menu button again to start adjustment. It will ask the gas type :
Gas type can be changed via pressing up and down arrow buttons. There are three gas type
supported by PPS Manager which are CO, NO2, LPG. Once decided press Menu button to continue. It
will show the current level:
Sel Gas
CO
Ext1 Lv:
040
Set Ext2
Sel Gas
CO
Ext2 Lv:
100