In case an error the fault LED will be activated together with fault relay at same time. Fault details
can be seen via pressing up and down buttons. The fault codes and details given in section XXX.
5.1 Automatic Test
Prosense PPS Manager simultaneously monitor all detectors connected to it. The FAULT relay and
LED will be activated in case any problem. Alarm and fault status can be monitored on the screen.
5.2 LED Test
Prosense PPS Manager has special function to test LEDs on front panel at any time. Press T button to
initiate test operation. Panel will activate all LEDs for moment and turn off all of them except on LED
as it is always blinking.
6. PROGRAMMING
The panel is already programmed and ready for using when shipped. User should adjust the gas type,
alarm settings for each detector. Each detector should be defined independently. These adjustments
can be done via using the keys near by LCD screen. The menu content includes below items:
Menu Item
Function
Set Ext1
Set fan1 relay alarm level
Set Ext2
Set fan2 relay alarm level
Set Alrm
Set alarm level
Actv Typ
Set alarm raising method
Gas Type
Set gas type of the detector
Language
Set Language
Scan Det
Start scanning detectors
Show Det
Show each detector status
Table 7
: Menu structer
6.1 Set FAN1 Relay Level:
To set alarm level for FAN1 press menu button to see menu items. The first item on menu is Set Ext1
to set level for FAN1:
Set Ext1