Prolon Control Systems
Lonbox PSW5000
Users Manual
Page 6
Functional Blocks
Node Object
Function block name:
“Node”
LonMark object type:
0
Number of blocks in device:
1
Principal network variable:
nvoStatus (SNVT_obj_status)
Network Variables
nviRequest
LonMark network variable type name: SNVT_obj_request
LonMark network variable type id:
92
nvoStatus
LonMark network variable type name: SNVT_obj_status
LonMark network variable type id:
93
Configuration Properties
Major Device Version
LonMark configuration property type:
165
LonMark configuration property name: SCPTdevMajVer
As defined by the LonMark standard this constant configuration property defines the major version
number of the device.
Devices with same major version number will have identical network interface. This means that if
any changes are made to the device network interface, the major version number will be
incremented.
Minor Device Version
LonMark configuration property type:
166
LonMark configuration property name: SCPTdevMinVer
As defined by the LonMark standard this constant configuration property defines the minor version
number for the device.
Digital Input Assignment
LonMark configuration property type:
167
LonMark configuration property name: UCPTdiAssignment
Default value:
1,2,3,4,(5,6)
Digital Input Switch Action
LonMark configuration property type:
168
LonMark configuration property name: SCPTdiSwitchAction
Default value:
SWA_DIM_UP_DOWN_OFF_ON_LEVEL