5. USE 

 

5.1. FUNCTIONS 

 
There are four functions which can be accessed 

with the “FUN” key. Every time this key is pressed, two 
out of the four functions will be displayed and the 
chosen function is reached by pressing from number 

1 to 4 plus the “ENTER” key. 

 

 

 

The Configuration and Timing functions contain 

the data which are specific of the installation the 
controller is destined to. It is normally programmed 
once, when mounting the unit and they are fixed in the 
memory indefinitely (they are usually programmed by 

the installer). 

The Manual and Total functions are the ones 

which are normally used by the user. 

 

 

5.2. CONFIGURATION 

 
The CONFIGURATION function adapts the unit to 

the installation asking the following questions: 

- Number of filters: Enter the number of filters of 

the cleaning sequence. 

- Time/Volume: These are the units the 

equipment works with. By “time”, it works in minutes 
and it is necessary to connect terminal 3 to the inputs 

so that it understands that water is circulating in the 
installation. By “volume”, it works with cubic metres 
and it is necessary to connect to input 1 a counter or a 
volumetric transmitter of impulses. 

- Between cleanings: These are the units 

(minutes or m3) the unit will take before it starts a 
cleaning. If a cleaning is started by pressure gauge or 
manually, while the equipment is counting these units, 
the counter of these units will be set at zero. The 

maximum value is 9999 minutes or m3. 

 
The following two values will only be asked if the 

unit was configured to work by volume: 

- Impulse value: is the value of the water which 

has circulated every time the volumetric counter gives 
an impulse. The value can go from 00.1 to 99.9 m3. 

- Maximum between impulses: is the maximum 

value in seconds that there can be between two 
impulses of the counter in order to detect a lack of 

water circulation and give 0 flow. The maximum value 
is 999 seconds. 

 
It is important 

to configure

 the unit after 

connecting it for the first time. 

 

 

(...)=(min),( m3),(seg). 

 
 

 

 

(by volume) 
 

(by volume) 
 
 
 
 

5.3.TIMINGS 

 

The TIMING function is used to give the time 

values, in seconds, to the unit. These values will allow 

the perfect working of the filter cleanings. Those 
values are as follows: 

  
- Filter 1 to n: Is the time it will take every filter to 

clean. The maximum time is 999 seconds and the 

values can be different for every filter. If a filter has a 
value 0, it will not be activated in the cleaning 
sequence. 

  
- Filter pause: Is the pause value between the 

end of a filter cleaning and the starting of the next one. 
The maximum value is 999 seconds. 

 
- Detection start by pressure gauge: Is the delay 

in the detection of the start by differential pressure 
gauge. The maximum value is 999 seconds. 

 

- Breakdown detection: Is the delay in the 

detection of a breakdown, which will only  be valid if 

the cleaning is taking place. The maximum value is 
999 seconds. 
 
 

Time:0    Volume:1=0  

Between clean=0000  

F1: Manual 

F2: Totals  

F3: Configuration 

F4: Timings  

CONFIGURATION:(...)  

Number of filters=00 

Impulse value = 00.0  

Máx.between imp.=000  

TIMINGS (seg) 

Filter 01 = 000 

Filter 02 = 000  

.../... 

Filter 18 = 000  

Filter pause = 000  

Detec. start pres=000 

Breakdown detect =000 

Содержание Agronic

Страница 1: ...re are 3 different models according to the number of filters to control for 6 12 and 18 filters Models for 6 and 12 filters can be increased whenever necessary up to 18 sending them back to the factor...

Страница 2: ...flow and volume total of filtered water For the detection of breakdowns in the installation For different options A timing for detection delay can be assigned to the inputs in order to avoid inadequa...

Страница 3: ...er and an opaque cover for the connection housing To maintain the isolation of the unit it is essential to keep the panels closed as well as to install grommets at the cable outlets which are provided...

Страница 4: ...that those cables supply other units or elements If the battery is far away from the controller use high section cables and make a reduction when entering the equipment The input is also protected wit...

Страница 5: ...rk properly a There is a black stripe on the screen Unplug the unit open it remove the keyboard and with a screwdriver cross the two contacts on the central part of the left side marked as J3 during t...

Страница 6: ...o the outputs see indicative stick Without the bridge the outputs are working to 12 Vdc and with the bridge installed they will have a voltage near to 24 volts From the company the units are delivered...

Страница 7: ...nsion for the Fulfilment of the Product Security The fulfilment of the following specifications was demonstrated as indicated in the Official Diary of the European Communities Emissions EN 50081 1 94...

Страница 8: ...will only be asked if the unit was configured to work by volume Impulse value is the value of the water which has circulated every time the volumetric counter gives an impulse The value can go from 00...

Страница 9: ...re gauge The third screen asks whether these data are to be erased by time by volume 5 6 CONSULTATION On pressing the CON key the following screen will be displayed The first screen shows the number o...

Страница 10: ...10 R 910 1...

Отзывы: