Progres Agronic Скачать руководство пользователя страница 4

 

3.2. CONNECTION 

 
The unit has to be installed following the 

prevailing regulations for electrical installations. 

In the “mounting box” model, the grommets 

provided with the unit are to be installed, removing the 
relevant dies (this should be done with the connection 

cover in place and screwed to avoid possible 
breakage). 

In the “build-in” model the terminals are placed at 

the back and they are the 
connector type. On placing 

the terminals check that they 
have been introduced in the 
guides, as it is shown in the 
figure. 

It is advisable to connect the cables to the 

terminals with terminal connections, which are also 
included with the unit. 

There is also a protection box for all the 

terminals, in case there is a risk of electrical sparks 
from storms entering the cables. 

 
 

3.2.1. SUPPLY TO THE EQUIPMENT 

 

Before connecting the unit, it is necessary to 

check its identification label where the characteristics 
of the power feeding are to be found. 

 

 

Power feeding at 220 Vac: 
A 6 amp magneto-thermal switch is to be included 

in the installation. It will be used as a disconnection 
device and it has to be placed near the unit and at an 
accessible place for the user. 

It is recommendable to do this as directly as 

possible, avoiding that the same cable supplies other 
sections. Use cable of the H05VV-F type, 1mm

2

A fuse (general fuse) and a varistor protect the 

mains input. The varistor might short-circuit the fuse 
automatically, on detecting an overload on the line 

(lightning, etc.); replace it with one of the same 
characteristics. 

For unstable or fluctuating voltages use grid 

stabilisers. 

If the unit is to be disconnected from the power line 

during several weeks, it is advisable to remove the 
bridge marked as “J4” (next to the battery) in the circuit 
placed behind the keyboard, and insert it again before 
connecting it to the power line. 

 

 

Power feeding at 12 Vdc: 
Check the polarity of the terminals. 
Connect two direct cables from the battery to the 

equipment feeding (+12-) avoiding that those cables 
supply other units or elements. 

If the battery is far away from the controller, use 

high section cables and make a reduction when 
entering the equipment. 

The input is also protected with a fuse and a 

varistor. 

To replace the fuse, half turn the fuse cover and 

insert another of the same value. 

 
 

3.2.2. CONNECTING THE EARTH TERMINAL 

 

The “build-in” model has a terminal screw to 

connect the protection earth terminal, and which is 
placed near the feeding terminals. 

In the “mounting box” model, a protection 

terminal is not needed, but it has got a box terminal 

marked as:  

CP

 to be connected to the earth 

terminal. 

Both the earth and box terminals are used to 

protect the unit by directing all electrical sparks 

produced by the internal gas discharger to the earth. 
These sparks can come in through the outlet cables. 

 
 

3.2.3. CONNECTING INPUTS 

 

The contacts that join the inputs with the 

common  have  to  be  normally  open  and  free  of 
tension. Avoid placing the cables of these inputs near 
power lines, dividing them into two separate groups. 

- TERMINAL NUMBER 3. Detector of flow 

circulation. In the version by time, connect a testing 
spike or external programmer or join it directly to 
terminal number 6 if circulation is continuous. In the 
version by volume connect a volumetric transmitter of 

impulses. 

- TERMINAL NUMBER 4. If the unit has a 

differential pressure gauge which detects when filters 
are dirty, connect it to this cleaning start input and to 
the common (CE). 

- TERMINAL NUMBER 5. Breakdown input to 

which one or several securities (maximum/minimum 
pressure gauges, etc…) will be connected, if 
necessary. These will only be accepted when a filter 

cleaning is taking place, leaving the unit out of work. 

- TERMINAL NUMBER 6 (CE). Input common. 

 
 

3.2.4 CONNECTING OUTLETS 

 

Connect the solenoids, relays, etc. between the 

common of outlets and the corresponding outlet.  

Do not surpass the charge per outlet and 

common.  

The “outlet fuse” protects from overloads and 

short-circuits. To change it, just half turn the cover of 
the fuse holder, take it out and replace it with a similar 
one. 

The outlets are isolated from the interior circuitry 

by relays and protected by a varistor in each one. 

 

 

Содержание Agronic

Страница 1: ...re are 3 different models according to the number of filters to control for 6 12 and 18 filters Models for 6 and 12 filters can be increased whenever necessary up to 18 sending them back to the factor...

Страница 2: ...flow and volume total of filtered water For the detection of breakdowns in the installation For different options A timing for detection delay can be assigned to the inputs in order to avoid inadequa...

Страница 3: ...er and an opaque cover for the connection housing To maintain the isolation of the unit it is essential to keep the panels closed as well as to install grommets at the cable outlets which are provided...

Страница 4: ...that those cables supply other units or elements If the battery is far away from the controller use high section cables and make a reduction when entering the equipment The input is also protected wit...

Страница 5: ...rk properly a There is a black stripe on the screen Unplug the unit open it remove the keyboard and with a screwdriver cross the two contacts on the central part of the left side marked as J3 during t...

Страница 6: ...o the outputs see indicative stick Without the bridge the outputs are working to 12 Vdc and with the bridge installed they will have a voltage near to 24 volts From the company the units are delivered...

Страница 7: ...nsion for the Fulfilment of the Product Security The fulfilment of the following specifications was demonstrated as indicated in the Official Diary of the European Communities Emissions EN 50081 1 94...

Страница 8: ...will only be asked if the unit was configured to work by volume Impulse value is the value of the water which has circulated every time the volumetric counter gives an impulse The value can go from 00...

Страница 9: ...re gauge The third screen asks whether these data are to be erased by time by volume 5 6 CONSULTATION On pressing the CON key the following screen will be displayed The first screen shows the number o...

Страница 10: ...10 R 910 1...

Отзывы: