Produal Oy
Copyright © 2020 Produal Oy - All rights reserved - 07/2020
PS
6001TRI
- 27/28
Web-site:
www.produal.com
Enquiries: T:
+358 10 219 9100
E:
40138
Language
Unsigned
0 = English (Default)
1 = Finnish
2 = Swedish
3 = French
4 = Italian
5 = Polish
6 = Spanish
7 = Catalan
8 = Euskera
40139
Sensor 1 Text (RI1/Network)
Default 0 = Disabled
Note: Disabled removes the text
and measurement from the display.
Unsigned
0 = Disabled
1 = Room
2 = Floor
3 = Outside
4 = Zone 1
5 = Zone 2
6 = Zone 3
7 = Bathroom
8 = Sauna
9 = Bedroom
10 = Kitchen
11 = Cooler
12 = Flow
13 = Hot Water
14 = Tank
15 = Pool
16 = Cabin
40140
Sensor 2 Text (RI2/Network)
Default: 0 = Disabled
Note: Disabled removes the text
and measurement from the display.
Unsigned
40141
Sensor 3 Text (Built-in / Network
Sensor)
Default: 1 = Room
Note: Disabled removes the text
and measurement from the display.
Unsigned
40142
Sensor 2 Source
Unsigned
0 = RI1
1 = Network Sensor (Default)
40159
Disable ECO Button User Cancel
Unsigned
0 = Enabled
1 = Disabled
40160
CO2 Calibration
REAL
-500...+500 ppm
40161
Y1 Output Mode
Default: Fan
Unsigned
0 = Network
1 = Sensor1 (RI1)
2 = Sensor2 (RI2)
3 = Sensor3 (Built-In)
4 = Setpoint
5 = Fan
6 = Humidity
7 = CO2
40162
Y2 Output Mode
Default: Setpoint
Unsigned
40163
Y3 Output Mode
Default: Sensor2 (Built-in)
Unsigned
40167
Display CO2
Unsigned
0 = Enabled
1 = Disabled
40168
Setpoint Limit Mode
Unsigned
0 = Absolute
1 = Relative
40169
AO Temp Scale
Unsigned
0.100 C/°F (Default 50)
40170
AO CO2 Scale
Unsigned
0..5000ppm (Default 5000)
40300
MAC ID
Unsigned
0..127
(Default 1)
40301
BACnet Baud Rate
Unsigned
0 = 9600 (Default)
1 = 19200
2 = 38400
3 = 57600
4 = 76800
5 = 115200
40304
Screen Refresh Rate
Unsigned
0 = Fast (Default)
1 = Medium
2 = Slow
40400
Force Reset
Unsigned
0 = Normal
1 = Force Reset
40401
Non Volatile Memory Update
Unsigned
0 = Normal
1 = Update
40403
Force Factory Defaults
Unsigned
0 = Normal
1 = Force Defaults