The maintenance mode password can be changed in the configuration settings. Make sure that
you note the new password if changed.
CONTROL SETTINGS
Parameter Name
Description
Range
Nominal Setpoint
Nominal Setpoint
0.0...99.9°C/°F/% (Default 21.0°C)
Setpoint Limit Mode
Setpoint Limit Mode
0 = Absolute (Default)
1 = Relative
Min Setpoint Adj
Absolute Mode: Minimum Adjustable Setpoint
Relative Mode: Minimum Setpoint Deviation from
Nominal Setpoint
0.0...99.9°C/°F/% (Default 14.0)
Max Setpoint Adj
Absolute Mode: Maximum Adjustable Setpoint
Relative Mode: Maximum Setpoint Deviation from
Nominal Setpoint
0.0...99.9°C/°F/% (Default 30.0)
INPUTS & OUTPUTS
Parameter Name
Description
Range
Sensor 1 Source
Sensor 1 Source. When set to Hardware reads RI1.
(status monitoring over the network is always active)
0 = Hardware (RI1)
1 = Network (Default)
Sensor 2 Source
Sensor 2 Source. When set to Hardware reads RI2.
(status monitoring over the network is always active)
0 = Hardware (RI1)
1 = Network (Default)
Sensor 3 Source
Sensor 3 Source. When set to Hardware reads the
internal temperature sensor.
(status monitoring over the network is always active)
0 = Hardware (Built-In Sensor) -
Default
1 = Network
Digital Input Mode
Digital Input Operation
(status monitoring over the network is active for all
modes)
0 = Disabled (no TRI effect)
1 = Close for ECO
2 = Open for ECO
3 = Close for OFF
4 = Open for OFF
5 = DI Contact Alarm
6 = Network
7 = Close for Night
8 = Disabled
Digital Input Delay
Digital Input Delay Timer (transition from active to
non-active)
0..7200 seconds (Default 0s)
Internal Sensor Cal
Internal Sensor One Point Compensation
-10.0..+10.0 °C/°F
RI1 Cal
Sensor Connected to RI1 Calibration
-10.0..+10.0 °C/°F
RI2 Cal
Sensor Connected to RI2 Calibration
-10.0..+10.0 °C/°F
Humidity Cal
Humidity Calibration
-10.0..+10.0 % rH
CO2 Cal.
CO2 Sensor Calibration (CO2 Models)
-500...+500 ppm
Y1 Mode
(TRI-3A Only)
Analogue Output Y1 Mode
Default: Fan
0 = Network
1 = Sensor1 (RI1)
2 = Sensor2 (RI2)
3 = Sensor3 (Built-In)
4 = Setpoint
5 = Fan
6 = Humidity
7 = CO2
Y2 Mode
(TRI-3A Only)
Analogue Output Y2 Mode
Default: Setpoint
Y3 Mode
(TRI-1R Only)
Analogue Output Y3 Mode
Default: Sensor3 (Bult-In Sensor)
AO Temp Scale (TRI-3A Only)
Temperature at 10V of Output
0..+100 °C/°F (Default 50)
AO CO2 Scale (TRI-3A Only)
CO2 at 10V Output
0..5000ppm (Default 5000)
Fan Night Speed
Fan Speed at Night (OFF Mode)
0..6 (Default 0)
OPERATING MODES
Parameter Name
Description
Range
Lock Mode
Lock Operation
0 = Disabled (default)
1 = On/Off/Boost Workable Only
2 = Temp Adjust Only Available
3 = No Input - All Buttons Disabled
Lock Code
Lock Mode Password
0000 - 9999 (default 0000)