www.usaprocom.com
200233-01B
10
INSTALLATION
Figure 6 - Mounting Clearances as
Viewed From Front of Heater
CEILING
36"
Minimum
6"
Minimum
From
Sides of
Heater
Left
Side
Right
Side
18" Minimum to Top Surface of Carpeting,
Tile or Other Combustible Material
FLOOR
CLEARANCES TO COMBUSTIBLES
DO NOT use an off the shelf 3/8"
NPT pipe plug. This will damage
the plungers located inside the
regulator.
DO NOT try to remove the plung-
ers from inside the regulator. The
plunger will be pushed back as
the fitting is installed.
Make sure the type of gas being
used is correct. Check to make sure
the connection fitting is in the cor-
rect inlet on the regulator. Refer to
Connecting to Gas Supply, page 13.
If you are using natural gas
and the pilot will not light, see
Troubleshooting, page 20.
Metal Cap
Metal Cap
DO NOT REMOVE
Yellow Natural Gas Plunger
Install Gas Fitting Here
2. Remove the metal cap installed over the
NG regulator inlet.
3. Install metal cap over LP/Propane regulator
inlet. This will keep debris out of regulator.
Use only the cap supplied on the
regulator. Do not use an off the
shelf pipe plug. This can damage
the plunger. The supplied regula-
tor cap is designed so it will not
engage the unused gas type.
4. Apply thread sealant to the threads on
the connection fitting. While pushing in,
rotate the fitting clockwise until the threads
engage the regulator. After the fitting has
been hand tightened into the regulator
use a wrench to complete tightening of the
fitting. Install additional fitting to connect
to the house supply.
Carefully follow the instructions below. This
heater is a freestanding unit designed to be
mounted on a wall or set on a base.
WARNING: Maintain the
minimum clearances shown in
Figure 6. If you can, provide
greater clearances from floor,
ceiling, and joining wall.