Main Power Connection
73
2. Associated Non-incendive Field Wiring Apparatus shall satisfy the following:
3. If the electrical parameters of the cable are unknown, the following values may
be used:
C
cable
= 196.85 pF/m (60 pF/ft)
L
cable
= 0.656
H/m (0.20
H/ft).
4. Wiring methods must be in accordance with the electrical code of the country in
use.
The PS-B unit must be installed in an enclosure. If installed in a Class I, Division 2
Location, the enclosure must be capable of accepting one or more Division 2 wiring
methods.
The PS-B unit is suitable for use in Class I, Division 2, Groups A, B, C, D and
provides non-incendive field wiring to apparatus in Class I, Division 2, Groups A, B,
C, D.
PS-B Unit
-
Associated Non-incendive Field
Wiring Apparatus (Mouse,
Keyboard)
V
oc
I
sc
C
a
L
a
V
max
I
max
C
i
+ C
cable
L
i
+ L
cable
DANGER
EXPLOSION HAZARD
Substitution of components may impair suitability for Division 2
hazardous(classified) locations.
Do not energize or disconnect the device while area is known to be hazardous.
The associated non-incendive field wiring apparatus shall not be connected in
parallel unless permitted by the associated non-incendive apparatus approval.
Failure to follow these instructions will result in death or serious injury.
Содержание PS-4000B Series
Страница 1: ...36 6HULHV 8VHU 0DQXDO...
Страница 12: ...PS 4000B Series User Manual 12...
Страница 14: ...PS 4000B Series User Manual 14...
Страница 60: ...PS 4000B Series User Manual 60...
Страница 74: ...PS 4000B Series User Manual 74...
Страница 95: ...Hardware Modifications 95 The following figure shows the dimensions of the UPS battery unit...
Страница 110: ...PS 4000B Series User Manual 110...
Страница 112: ...PS 4000B Series User Manual 112...
Страница 132: ...PS 4000B Series User Manual 132...
Страница 134: ...PS 4000B Series User Manual 134...
Страница 138: ...PS 4000B Series User Manual 138...