PS-4000B Series User Manual
66
Grounding Procedure
The PS-B functional ground has 2 connections:
Supply voltage
Ground connection
When grounding, follow the procedure below:
Step
Action
1
Check that the grounding resistance is 100
or less.
2
When connecting the SG line to another device, ensure that the design of the
system/connection does not produce a ground loop.
Note: The SG and FG terminals are connected internally in the PS-B unit.
3
Use 2.5 mm
2
(13 AWG) wire to make the ground connection.
Create the connection point as close to PS-B unit as possible and make the wire
as short as possible.
Содержание PS-4000B Series
Страница 1: ...36 6HULHV 8VHU 0DQXDO...
Страница 12: ...PS 4000B Series User Manual 12...
Страница 14: ...PS 4000B Series User Manual 14...
Страница 60: ...PS 4000B Series User Manual 60...
Страница 74: ...PS 4000B Series User Manual 74...
Страница 95: ...Hardware Modifications 95 The following figure shows the dimensions of the UPS battery unit...
Страница 110: ...PS 4000B Series User Manual 110...
Страница 112: ...PS 4000B Series User Manual 112...
Страница 132: ...PS 4000B Series User Manual 132...
Страница 134: ...PS 4000B Series User Manual 134...
Страница 138: ...PS 4000B Series User Manual 138...