Maintenance

•  Inspect the cable at the beginning of every heating season and monthly during operation. Check for evidence of cutting, tearing or 
  other signs of wear.
•  Checks should also be done after any maintenance has been performed.
•  Check the heating cable to verify that the insulation is not wet. Wet sections of pipe can result in cold spots or frozen sections. If the 
  insulation is damp or wet, it should be replaced.
•  Turn off or disconnect the power when the heating season ends. Reconnect before the next heating season.

     

Warning:  

Disconnect the power connection before inspecting or performing any maintenance.

!

English

8

Problem

 
Circuit Breaker Trips

Icing Problems Persist

Probable Cause

 
Circuit is undersized

Defective circuit breaker

Internal or external damage to 
the cable causing a short.

Pattern not laid out correctly

Loss of power

Damaged Bi-Metallic 
thermostat

External heat source

Solution

 
Have a licensed electrician install new circuit breaker with an appropriate 
current (amp) rating.

Unplug the cable and check for cuts, if no cuts exist on the exterior, there 
may be cuts on the inside. If all other solutions have been checked and the 
cable is still tripping the circuit breaker. Dispose of the cable and purchase 
a new cable to protect the pipe.

Look for areas that deviate from the installation instructions and change 
accordingly.

Check the PRIMELIGHT

®

 Indicator Light, if the light is still on, the cable is 

still receiving power.

If the thermostat is damaged, the unit must be replaced. To test the 
thermostat, first check that power is being supplied to the cord and that 
the cord is not overlapping itself. Wrap an ice pack around the thermostat 
while it is installed on the pipe. After a few minutes the cable should be 
warm to the touch. If the cable does not respond to the ice pack it is 
defective and needs to be replaced.

Be sure to prevent external heat sources from coming in contact or being in 
close proximity with the cable. If an external heat source is close to the 
thermostat, it may prevent the thermostat from registering sub 40°F/4°C 
temperatures, preventing it from turning on the heated portion of the cable.

Troubleshooting

Содержание PHC126W18

Страница 1: ...English Water Pipe Freeze Protection Installation Operating Instructions Prime Wire Cable Inc Cerritos CA 90703 Service Servicio 888 445 9955...

Страница 2: ...o the cable even when not heating this allows you to check the status of the pipe cable at any time even when it is not cold enough to trigger the thermal cutoff Prime Water Pipe Freeze Protection App...

Страница 3: ...st be installed in compliance with the National Electrical Code and Canadian Electrical Code Ground fault protection GFCI is required If an outlet does not exist close enough to the pipe to plug in th...

Страница 4: ...6 2 6 2 6 9 2 6 2 6 2 6 2 6 2 6 10 2 6 2 6 2 6 2 6 2 6 11 2 6 2 6 2 6 2 6 2 6 12 1 12 1 12 1 12 1 12 1 12 13 1 12 1 12 1 12 1 12 1 12 14 1 12 1 12 1 12 1 12 1 6 1 12 1 6 15 1 12 1 6 1 12 1 6 1 12 1 6...

Страница 5: ...metallic braid Minimum resistance should be 20 megohms Readings below 20 megohms may mean the electrical insulation has been damaged Replace the heating cable if readings are below 20 megohms Once ins...

Страница 6: ...e pipe Hand tightened plastic wire ties which have a temperature rating higher than 175 F 79 4 C may also be used to fasten the cable to pipes For a plastic pipe system wrapping the plastic pipe with...

Страница 7: ...that Is a circuit with an appropriate current amp amperage rating to support the selected heating cable The cable should not be more than 80 of the circuit s total amp rating A circuit for a cable dra...

Страница 8: ...e current amp rating Unplug the cable and check for cuts if no cuts exist on the exterior there may be cuts on the inside If all other solutions have been checked and the cable is still tripping the c...

Страница 9: ...f purchase by the Consumer to Attention Quality Assurance Manager Prime Wire Cable Inc 280 Machlin Court 2nd Floor City of Industry California 91789 and if after analysis and review by Prime s QC Depa...

Страница 10: ...10 Protection antigel pour canalisations d eau Installation et mode d emploi Prime Wire Cable Inc Cerritos CA 90703 Service Servicio 888 445 9955 les Fran cais...

Страница 11: ...ermet de v rifier tout moment le statut du c ble pour canalisation m me lorsqu il ne fait pas assez froid pour d clencher le blocage thermique Application de la protection antigel pour canalisations d...

Страница 12: ...ns doivent tre install s conform ment au NEC National Electric Code et ou au Code canadien de l lectricit Un disjoncteur de fuite de terre diff rentiel est requis S il n existe pas de prise suffisamme...

Страница 13: ...5 6 1 6 1 6 1 6 1 6 1 6 7 1 6 1 6 1 6 1 6 1 6 8 1 6 1 6 1 6 2 6 2 6 9 2 6 2 6 2 6 2 6 2 6 10 2 6 2 6 2 6 2 6 2 6 11 2 6 2 6 2 6 2 6 2 6 12 1 12 1 12 1 12 1 12 1 12 13 1 12 1 12 1 12 1 12 1 12 14 1 12...

Страница 14: ...sistance minimale doit tre de 20 m gohms Les lectures inf rieures 20 m gohms peuvent signifier que l isolation lectrique a t endommag e Remplacer le c ble chauffant si les lectures sont inf rieures 20...

Страница 15: ...errage manuel dont la temp rature nominale est sup rieure 175 F 79 4 C peuvent aussi tre utilis s pour fixer le c ble aux canalisations Pour un syst me de canalisations en plastique il suffit d entour...

Страница 16: ...c a qui Est un circuit avec un courant nominal appropri A amp rage pour le c ble chauffant s lectionn Le c ble ne doit pas repr senter plus de 80 de l amp rage nominal total du circuit Le circuit d un...

Страница 17: ...r un lectricien agr d installer un nouveau disjoncteur avec un courant nominal amp rage appropri D brancher le c ble et v rifier l absence de coupures S il n y a aucune coupure l ext rieur il peut y e...

Страница 18: ...t pay avec la preuve d achat Attention Quality Assurance Manager Prime Wire Cable Inc 280 Machlin Court 2nd Floor City of Industry Californie 91789 tats Unis et si apr s analyse et examen par le d par...

Страница 19: ...Protecci n anticongelamiento de tuber as de agua Instrucciones de instalaci n y operaci n Prime Wire Cable Inc Cerritos CA 90703 Service Servicio 888 445 9955 Espa ol 19...

Страница 20: ...cibiendo suministro incluso cuando no est calentando esto le permite revisar el estado del cable de la tuber a en cualquier momento incluso cuando no hace fr o suficiente para activar el limitador t r...

Страница 21: ...s calefactores de tuber as deben instalarse en conformidad con el C digo El ctrico Nacional y o el C digo El ctrico Canadiense Se requiere protecci n con descarga a tierra GFCI Si no hay un tomacorrie...

Страница 22: ...1 6 1 6 1 6 1 6 1 6 8 1 6 1 6 1 6 2 6 2 6 9 2 6 2 6 2 6 2 6 2 6 10 2 6 2 6 2 6 2 6 2 6 11 2 6 2 6 2 6 2 6 2 6 12 1 12 1 12 1 12 1 12 1 12 13 1 12 1 12 1 12 1 12 1 12 14 1 12 1 12 1 12 1 12 1 6 1 12 1...

Страница 23: ...a del cable calefactor La resistencia m nima debe ser de 20 megaohmios Las lecturas inferiores a 20 megaohmios pueden significar que el aislamiento est da ado Reemplace el cable calefactor si las lect...

Страница 24: ...res de pl stico cuya temperatura nominal sea superior a 175 F 79 4 C a fin de sujetar el cable a las tuber as Para un sistema de tuber as de pl stico envolver la tuber a con papel de aluminio antes de...

Страница 25: ...120 voltios CA que Sea un circuito con una corriente nominal amperios amperaje adecuada para soportar el cable calefactor seleccionado El cable no debe superar el 80 del amperaje total del circuito U...

Страница 26: ...ta con licencia que instale un cortacircuito nuevo con capacidad nominal amperios correcta Desenchufe el cable y busque si tiene cortes si no hay cortes en el exterior puede haberlos en el interior Si...

Страница 27: ...pra a la siguiente direcci n Attention Quality Assurance Manager Prime Wire Cable Inc 280 Machlin Court 2nd Floor City of Industry California 91789 y si tras el an lisis y revisi n por parte del Depar...

Страница 28: ......

Отзывы: