Product Overview

General ......................................................................... 1

Receiving Inspection ..................................................... 1

Wiring ........................................................................... 1

Installation Instructions

Installing the RDV/RDVQ 5000 Terminal Unit ................. 2

Air Volume Ranges ........................................................ 2 

SP300 Cal. Curves - RDV ............................................. 3

SP300 Cal. Curves - RDVQ w/Absorptive Silencer ........ 4

SP300 Cal. Curves - RDVQ w/Packless Silencer ........... 5

AIR VOLUME CONTROL VALVE

TABLE OF CONTENTS

Содержание RDV Series

Страница 1: ...v004 Issue Date 07 14 16 2016 Price Industries Limited All rights reserved MANUAL INSTALLATION OPERATION AND MAINTENANCE Air Volume Control Valve RDV RDVQ Series ...

Страница 2: ...ring 1 Installation Instructions Installing the RDV RDVQ 5000 Terminal Unit 2 Air Volume Ranges 2 SP300 Cal Curves RDV 3 SP300 Cal Curves RDVQ w Absorptive Silencer 4 SP300 Cal Curves RDVQ w Packless Silencer 5 AIR VOLUME CONTROL VALVE TABLE OF CONTENTS ...

Страница 3: ...open position An identification mark on the end of the shaft indicates the damper position The factory supplied sensing lines are color coded Red indicates the total pressure or HI line which should be located on the upstream side Green indicates the static pressure or LO line which should be located on the downstream side An optional protective enclosure may be provided to house the terminal unit...

Страница 4: ...ended Stability and accuracy may not be acceptable at lower than recommended air flow limits The actual performance will vary depending on the terminal unit controls supply RDV Basic Size CFM L S MIN MAX MIN MAX 4 45 225 21 106 5 60 350 28 165 6 65 450 31 212 7 95 650 45 307 8 125 800 59 378 9 160 1050 76 496 10 210 1350 99 637 12 300 2100 142 991 14 430 3000 203 1416 16 575 4000 271 1888 RDVQ Abs...

Страница 5: ...locity controls utilize a flow through transducer a proper velocity pressure reading will NOT be read at the gauge taps and the calibration curves CANNOT be used for field measurement The flow through transducer operates on the principle of mass flow rather than pressure differential Controls utilizing a dead ended pressure transducer will allow field measurement with the gauge taps and calibratio...

Страница 6: ...trols utilizing a dead ended pressure transducer will allow field measurement with the gauge taps and calibration curves provided 2 Setting flow limits for a differential pressure of less than 0 02 inches is NOT recommended Stability and accuracy of flow limits may not be acceptable due to low velocity pressure signal Performance will vary depending on the terminal unit controls provided 3 For fie...

Страница 7: ...ill allow field measurement with the gauge taps and calibration curves provided 2 Setting flow limits for a differential pressure of less than 0 02 inches is NOT recommended Stability and accuracy of flow limits may not be acceptable due to low velocity pressure signal Performance will vary depending on the terminal unit controls provided 3 For field calibration of air flow limits refer to the con...

Страница 8: ...is document contains the most current product information as of this printing For the most up to date product information please go to priceindustries com 2016 Price Industries Limited All rights reserved ...