Installing the RDV/RDVQ Terminal Unit
The basic RDV is light enough that it can be supported by the
ductwork in which it is installed. The RDVQ is supplied with
silencers and should be supported directly. Use the support
method prescribed for the round duct in the job specifications.
NOTE:
For optimum performance there should be a minimum
of three duct diameters of straight inlet duct, same size as the
inlet, between the inlet and any transition, take off or fitting.
The assembly should be mounted right side up. It should be
level within ±10 degrees of horizontal, both parallel to the
air flow and at right angles to the air flow. The side of the
assembly is labelled with an arrow indicating UP. Do not mount
the control side of the assembly tight to a wall, pipe or other
obstruction. Allow sufficient room for access to the controls
If the RDV/RDVQ is mechanically fastened to the duct work an
approved duct sealer should be used to seal all connections.
Damper rotation is always clockwise to the open position.
An identification mark on the end of the shaft indicates the
damper position.
The air volume ranges listed are recommended for optimum
performance. A minimum value of zero is also acceptable if no
heating coils are attached.
Selection of air flow limits below the listed values is not
recommended. Stability and accuracy may not be acceptable
at lower than recommended air flow limits. The actual
performance will vary depending on the terminal unit controls
supply.
RDV Basic
Size
CFM
L/S
MIN
MAX
MIN
MAX
4
45
225
21
106
5
60
350
28
165
6
65
450
31
212
7
95
650
45
307
8
125
800
59
378
9
160
1050
76
496
10
210
1350
99
637
12
300
2100
142
991
14
430
3000
203
1416
16
575
4000
271
1888
RDVQ - Absorptive
Size
CFM
L/S
MIN
MAX
MIN
MAX
4
--
--
--
--
5
--
--
--
--
6
80
450
38
212
7
110
650
52
307
8
160
800
76
378
9
200
1050
94
496
10
270
1350
127
637
12
350
2100
165
991
14
500
3000
236
1416
16
650
4000
307
1888
RDVQ - Absorptive
Size
CFM
L/S
MIN
MAX
MIN
MAX
4
--
--
--
--
5
--
--
--
--
6
65
380
31
179
7
95
650
45
307
8
125
790
59
373
9
160
1050
76
496
10
210
1350
99
637
12
300
2025
142
956
14
430
2400
203
1133
16
575
3425
271
1616
Air Volume Ranges
2
AIR VOLUME CONTROL VALVE - Manual
|
priceindustries.com
AIR VOLUME CONTROL VALVE
INSTALLATION INSTRUCTIONS
NOTE:
Factory calibrated controls must be selected
within the above flow range limits. A minimum value
of zero is also available. When an auxiliary flow
setting is specified, the value must be greater than
the minimum setting and within the range limits.
On controls mounted by Price but supplied by others, the air
volume ranges are guidelines only.
Selection of air flow limits below the listed values is not
recommended. Stability and accuracy may not be acceptable
at lower than recommended air flow limits. The actual
performance will vary depending on the terminal unit controls
supplied.