Installing the RDV/RDVQ Terminal Unit

The basic RDV is light enough that it can be supported by the 
ductwork in which it is installed. The RDVQ is supplied with 
silencers and should be supported directly. Use the support 
method prescribed for the round duct in the job specifications.

NOTE:

 For optimum performance there should be a minimum 

of three duct diameters of straight inlet duct, same size as the 
inlet, between the inlet and any transition, take off or fitting.

The assembly should be mounted right side up. It should be 
level within ±10 degrees of horizontal, both parallel to the 
air flow and at right angles to the air flow. The side of the 
assembly is labelled with an arrow indicating UP. Do not mount 
the control side of the assembly tight to a wall, pipe or other 
obstruction. Allow sufficient room for access to the controls

If the RDV/RDVQ is mechanically fastened to the duct work an 
approved duct sealer should be used to seal all connections.

Damper rotation is always clockwise to the open position. 
An identification mark on the end of the shaft indicates the 
damper position. 

The air volume ranges listed are recommended for optimum 
performance. A minimum value of zero is also acceptable if no 
heating coils are attached.

Selection of air flow limits below the listed values is not 
recommended. Stability and accuracy may not be acceptable 
at lower than recommended air flow limits. The actual 
performance will vary depending on the terminal unit controls 
supply.

RDV Basic 

 

 

 

Size

CFM

L/S

MIN

MAX

MIN

MAX

4

45

225

21

106

5

60

350

28

165

6

65

450

31

212

7

95

650

45

307

8

125

800

59

378

9

160

1050

76

496

10

210

1350

99

637

12

300

2100

142

991

14

430

3000

203

1416

16

575

4000

271

1888

RDVQ - Absorptive

Size

CFM

L/S

MIN

MAX

MIN

MAX

4

--

--

--

--

5

--

--

--

--

6

80

450

38

212

7

110

650

52

307

8

160

800

76

378

9

200

1050

94

496

10

270

1350

127

637

12

350

2100

165

991

14

500

3000

236

1416

16

650

4000

307

1888

RDVQ - Absorptive

Size

CFM

L/S

MIN

MAX

MIN

MAX

4

--

--

--

--

5

--

--

--

--

6

65

380

31

179

7

95

650

45

307

8

125

790

59

373

9

160

1050

76

496

10

210

1350

99

637

12

300

2025

142

956

14

430

2400

203

1133

16

575

3425

271

1616

Air Volume Ranges

2

AIR VOLUME CONTROL VALVE - Manual 

  |   

priceindustries.com

AIR VOLUME CONTROL VALVE

INSTALLATION INSTRUCTIONS

NOTE:

 

Factory calibrated controls must be selected 

within the above flow range limits. A minimum value 
of zero is also available. When an auxiliary flow 
setting is specified, the value must be greater than 
the minimum setting and within the range limits.

On controls mounted by Price but supplied by others, the air 
volume ranges are guidelines only.

Selection of air flow limits below the listed values is not 
recommended. Stability and accuracy may not be acceptable 
at lower than recommended air flow limits. The actual 
performance will vary depending on the terminal unit controls 
supplied.

Содержание RDV Series

Страница 1: ...v004 Issue Date 07 14 16 2016 Price Industries Limited All rights reserved MANUAL INSTALLATION OPERATION AND MAINTENANCE Air Volume Control Valve RDV RDVQ Series ...

Страница 2: ...ring 1 Installation Instructions Installing the RDV RDVQ 5000 Terminal Unit 2 Air Volume Ranges 2 SP300 Cal Curves RDV 3 SP300 Cal Curves RDVQ w Absorptive Silencer 4 SP300 Cal Curves RDVQ w Packless Silencer 5 AIR VOLUME CONTROL VALVE TABLE OF CONTENTS ...

Страница 3: ...open position An identification mark on the end of the shaft indicates the damper position The factory supplied sensing lines are color coded Red indicates the total pressure or HI line which should be located on the upstream side Green indicates the static pressure or LO line which should be located on the downstream side An optional protective enclosure may be provided to house the terminal unit...

Страница 4: ...ended Stability and accuracy may not be acceptable at lower than recommended air flow limits The actual performance will vary depending on the terminal unit controls supply RDV Basic Size CFM L S MIN MAX MIN MAX 4 45 225 21 106 5 60 350 28 165 6 65 450 31 212 7 95 650 45 307 8 125 800 59 378 9 160 1050 76 496 10 210 1350 99 637 12 300 2100 142 991 14 430 3000 203 1416 16 575 4000 271 1888 RDVQ Abs...

Страница 5: ...locity controls utilize a flow through transducer a proper velocity pressure reading will NOT be read at the gauge taps and the calibration curves CANNOT be used for field measurement The flow through transducer operates on the principle of mass flow rather than pressure differential Controls utilizing a dead ended pressure transducer will allow field measurement with the gauge taps and calibratio...

Страница 6: ...trols utilizing a dead ended pressure transducer will allow field measurement with the gauge taps and calibration curves provided 2 Setting flow limits for a differential pressure of less than 0 02 inches is NOT recommended Stability and accuracy of flow limits may not be acceptable due to low velocity pressure signal Performance will vary depending on the terminal unit controls provided 3 For fie...

Страница 7: ...ill allow field measurement with the gauge taps and calibration curves provided 2 Setting flow limits for a differential pressure of less than 0 02 inches is NOT recommended Stability and accuracy of flow limits may not be acceptable due to low velocity pressure signal Performance will vary depending on the terminal unit controls provided 3 For field calibration of air flow limits refer to the con...

Страница 8: ...is document contains the most current product information as of this printing For the most up to date product information please go to priceindustries com 2016 Price Industries Limited All rights reserved ...

Отзывы: