RCI-100 Configuration:
The RCI-100 requires no configuration other than for its communication fail operation. In the event of a
communications failure on the communications board, the RCI-100 can be set up to take various
actions on its outputs. This may be desirable in order to place connected devices into a safe operating
mode. By default factory setting, all outputs remain at their last known state if a communications failure
occurs.
* If SW2-3=CLOSED then the analog output will ramp to the setting of K1.
The output will change at a rate determined by the setting of K2. The
settings of the trim pots can be read on test points TP
1,2
using a
voltmeter. The test points read a voltage of 0-5V for a 0-100%
adjustment.
where,
Output
= 0-20 (mA) and
Ramp Rate
= 0-60 (seconds) (5 sec. minimum)
SW2-
Function
OPEN
CLOSED
1
Relay Fail Mode
No Change
See SW2-2
2 Relay
Fail
Status De-Energize Energize
3
Output Fail Mode
No Change
Ramp to K1*
4
5
6 Battery
Charger Off
On
7 I/O
Calibration
8 I/O
Calibration
Volt
Output
TP
5
20
1
×
=
Volt
RampRate
TP
5
60
2
×
=