PAC-M200-A Interface Module for PremiSys
®
Air Products
8
Using Dip switch SW3 and SW4 to adjust Outdoor Reset Function
Located in the PAC-M200-A Interface Module
Outdoor air reset function temperature Range
Outdoor Ambient
50° F - 75° F
Supply Air Setpoint
50° F - 75° F
Switch Position
OFF
ON
1 2 3 4 5
Higher Setpoint
6 7 8 9 10
Lower Setpoint
70F Fac. Setting
55F Fac. Setting
50
50
51
51
52
52
53
53
54
54
55
55
56
56
57
57
58
58
59
59
60
60
61
61
62
62
63
63
64
64
65
65
66
66
67
67
68
68
69
69
70
70
71
71
72
72
73
73
74
74
75
75
1 2 3 4 5
Higher Setpoint
6 7 8 9 10
Lower Setpoint
65F Fac. Setting
55F Fac. Setting
50
50
51
51
52
52
53
53
54
54
55
55
56
56
57
57
58
58
59
59
60
60
61
61
62
62
63
63
64
64
65
65
66
66
67
67
68
68
69
69
70
70
71
71
72
72
73
73
74
74
75
75
SW3 -
SW3 -
SW4 Dip Switch Settings
Supply air Setpoint
SW3 Dip Switch Settings
Outdoor Air Temperature
SW4 -
SW4 -
70F
70F
65F
65F
60F
60F
55F
55F
50F
50F
45F
45F
50F
55F
60F
65F
70F
Outdoor Air Temperature
Supply Air
Setpoint
Outdoor Air Reset Function
Factory Setting
Higher
Lower
70F
70F
65F
65F
60F
60F
55F
55F
50F
50F
45F
45F
50F
55F
60F
65F
70F
Outdoor Air Reset Function
Factory Setting
Supply Air
Setpoint
Outdoor Air Temperature
Higher
Lower
Outdoor Reset Function
Use DIP Switch SW3 and SW4 to Adjust Outdoor Reset Function located in the PAC-M200-A Interface Module.
Module Outdoor Air Reset Function Temperature Range
Outdoor Air
50° F - 75° F
Supply Air Setpoint 50° F - 75° F
Using Dip switch SW3 and SW4 to adjust Outdoor Reset Function
Located in the PAC-M200-A Interface Module
Outdoor air reset function temperature Range
Outdoor Ambient
50° F - 75° F
Supply Air Setpoint
50° F - 75° F
Switch Position
OFF
ON
1 2 3 4 5
Higher Setpoint
6 7 8 9 10
Lower Setpoint
70F Fac. Setting
55F Fac. Setting
50
50
51
51
52
52
53
53
54
54
55
55
56
56
57
57
58
58
59
59
60
60
61
61
62
62
63
63
64
64
65
65
66
66
67
67
68
68
69
69
70
70
71
71
72
72
73
73
74
74
75
75
1 2 3 4 5
Higher Setpoint
6 7 8 9 10
Lower Setpoint
65F Fac. Setting
55F Fac. Setting
50
50
51
51
52
52
53
53
54
54
55
55
56
56
57
57
58
58
59
59
60
60
61
61
62
62
63
63
64
64
65
65
66
66
67
67
68
68
69
69
70
70
71
71
72
72
73
73
74
74
75
75
SW3 -
SW3 -
SW4 Dip Switch Settings
Supply air Setpoint
SW3 Dip Switch Settings
Outdoor Air Temperature
SW4 -
SW4 -
70F
70F
65F
65F
60F
60F
55F
55F
50F
50F
45F
45F
50F
55F
60F
65F
70F
Outdoor Air Temperature
Supply Air
Setpoint
Outdoor Air Reset Function
Factory Setting
Higher
Lower
70F
70F
65F
65F
60F
60F
55F
55F
50F
50F
45F
45F
50F
55F
60F
65F
70F
Outdoor Air Reset Function
Factory Setting
Supply Air
Setpoint
Outdoor Air Temperature
Higher
Lower
© 2015 Mitsubishi Electric US, Inc.
Premi
Sys