AFV
+
Series High Power Programmable AC Power Supply
6-110
6.3.16
SOUR:SOFT:TIME
Function Description
:
Setup Delay Time and Ramp Time of Soft Start function
Command Description
:
SOUR:SOFT:TIME 5.00,3.00\r\n
Parameter1
:
Delay Time
Parameter2
:
Ramp Time
Answer Command
:
None
6.4
FUNC Command
Function Description
:
Select operation function mode
Command Description
:
FUNC GEN|STEP|GARD|THR|LVRT|TRAN\r\n
Parameter1
:
Function abbreviation
GEN- General Mode
STEP- Step Mode
GRAD- Gradual Mode
THR- Three Phase Independent Output
SOFT- Soft Start
Answer Command
:
None
NOTE
:
Before send the “OUTPut” Command, please select operation function
mode.
6.5
INST Command
6.5.1
INST:COUPling
Function Description
:
Setup Three-Phase Synchronized / Three-Phase Independent
Voltage Mode
Command Description
:
INST:COUP 0|1\r\n
Parameter1
:
Setup voltage operation mode (0—Three-Phase Synchronized,
1—Three-Phase Independent)
Answer Command
:
None