background image

charging and collecting stages.  This assures that all
system air is filtered.

Conventional media filters rely on fiber density for par-
ticulate removal efficiency.  A media filter is rated effi-
ciency is based on the average efficiency over the fil-
ter is life.  Since the initial filter efficiency is lower than
the rated efficiency, a substantial amount of particles
go unfiltered.  In contrast, PurePac delivers the rated
efficiency instantly and continuously.  The high-densi-
ty charging and collecting zones produce an immedi-
ate and constant removal rate regardless of particle
size. 

Reliability

The PurePac uses a programmable logic controller
(PLC) for system control and monitoring, in conjunc-
tion with high frequency electronics, to deliver opti-
mum performance and assure the highest degree of
reliability.

The versatile control system can be easily integrated
with existing building management systems, adding
another degree of reliability in the overall building sys-
tem.

The durable, all aluminum 2-stage electronic collec-
tors feature unitary construction and are designed to
last the lifetime of the system.  The integrated auto-
matic wash system assures optimum performance
and maximum system reliability.

Value

PurePac's design features increased collector surface
area in a smaller package compared to conventional
systems, resulting in higher dirt holding capacities and
reduced system footprint.  This translates into extra

available floor space, up to 30% in some instances.

PurePac's low resistance to airflow results in reduced
fan horsepower and fan energy cost.  Over a period of
time, this reduction amounts to significant savings in
energy costs.  Since PurePac uses wash-in-place
electronic collectors, replacement filter cost, disposal
cost and labor cost are eliminated.

When it comes to value, PurePac delivers.  High per-
formance and reliability in a compact design, and low
operating cost make PurePac the ideal choice for
today's IAQ challenges. Call us, and we'll prepare a
life cycle cost comparison for your filtration system
and show you how PurePac can deliver performance,
reliability and value.

System Description

PurePac Front Access Model (FA) is packaged as a
complete system, including the electronic air purifier,
system control, detergent dispenser and system
accessories.  Components are furnished factory
assembled, except for the electronic air purifier, which
is shipped knocked-down for field installation inside
the air handler or ventilation duct.

PurePac Model FA uses Flanders type HCC electron-
ic collectors and modular design, arranged in multiple
tiers and varying widths to attain the specified capac-
ities and efficiency.  The versatile design and modular
construction can accommodate all sizes of ventilation
systems by installing multiple units side-by-side.

PurePac Delivers

Flanders Precisionaire - Foremost in Air Filtration            

Engineered Products: 1-800-637-2803     Replacement Products: 1-800-347-2220

Содержание PB1900-0604

Страница 1: ...oor air Configuration PurePac Side Access units are available in sizes ranging from 3 000 to 30 000 cfm Housings are 16 gauge galvanealed steel continuously welded primed and painted Pre and post mist eliminators electronic collectors and built in cleaning system are factory assembled into the housing PLC control and detergent dispenser are supplied as separate compo nents PurePac front access uni...

Страница 2: ...onal loose granular carbon filters The disposable HMZD panels also offer clean easy removal and replacement The operating cost to move ventilation air through a fil tration system is directly related to the filter is resist ance PurePac s low and constant 0 25î w g resist ance results in reduced fan horsepower and a signifi cant energy savings compared to conventional filtra tion Since PurePac s e...

Страница 3: ...g capacities and reduced system footprint This translates into extra available floor space up to 30 in some instances PurePac s low resistance to airflow results in reduced fan horsepower and fan energy cost Over a period of time this reduction amounts to significant savings in energy costs Since PurePac uses wash in place electronic collectors replacement filter cost disposal cost and labor cost ...

Страница 4: ...with the following standard accessories Wash water strainer 1 each Ball valve 1 each Backflow preventer 1 each Solenoid valve 1 each Access door electrical interlock pilot light 2 each Detergent 55 gal Utilities Electrical Standard 120 Vac 1 ph 60 Hz Optional 208 230 460 Vac 1 ph 50 60 Hz Wash Water See Selection Table gpm 40 psig System Drain Sized according to applicable codes to handle water an...

Страница 5: ...5 90 85 H W gpm gal lb FA 0604 22 8 10 000 12 500 14 000 77 3 8 50 3 8 28 8 1 4 1 025 FA 0605 28 32 12 500 15 500 17 500 77 3 8 61 3 16 36 1 8 1 160 FA 0606 33 84 15 000 18 000 21 000 77 3 8 72 43 2 2 2 1 295 FA 0804 30 4 13 500 16 500 18 500 102 5 8 50 3 8 38 4 1 9 1 250 FA 0805 37 76 16 500 20 500 23 000 102 5 8 61 3 16 48 2 4 1 540 FA 0806 45 12 20 000 24 500 27 500 102 5 8 72 57 6 2 9 1 740 FA...

Страница 6: ...minators electronic collectors integral wash system and electrically interlocked access door Options PurePac Model SA is available with TechSorb HMZD bonded activated carbon panels for gas phase control The TechSorb is contained in a sepa rate cabinet that conveniently bolts to the exhaust side of the Model SA cabinet The panels are arranged in a V Bank configuration using fully gasketed tracks to...

Страница 7: ...6 000 7 000 40 1 4 76 31 1 2 14 4 0 7 785 SA 0403 11 3 5 000 6 000 7 000 64 1 8 41 7 8 55 3 8 14 4 0 7 710 SA 0404 15 2 6 500 8 000 9 500 64 1 8 54 3 8 55 3 8 19 2 1 810 SA 0405 18 9 8 500 10 000 11 500 64 1 8 65 1 8 55 3 8 24 1 2 930 SA 0406 22 6 10 000 12 000 14 000 64 1 8 76 55 3 8 28 8 1 4 1 110 SA 0407 26 4 11 500 14 500 16 500 64 1 8 88 5 8 55 3 8 33 6 1 7 1 225 SA 0408 30 13 000 16 000 18 5...

Страница 8: ...g System Water detergent washing system shall be high pressure low volume type Detergent wash and rinse water shall be applied by oscillating copper manifolds containing brass spray nozzles located on both the air entering and air leaving side of each module tier Complete effective washing of all ion izing collector cell surfaces and all appurtenances shall be provided Drive motors used to oscilla...

Отзывы: