– 14 –
Step 2:
Press the
(up arrow key) or
(down arrow
key) until the word UPDATE appears.
Step 3:
Press Enter.
Step 4:
Press the
(up arrow key) or
(down arrow
key) to select an update rate.
Step 5:
Press ENTER to finalize the selection.
DAMP
or dampening: with five different options, this mode
allows for taking process pressure readings and averaging
them. This option is particularly useful to stabilize minor
process fluctuations. The options are NONE*, AVG 8, AVG
6, AVG 4, AVG 2.
Step 1:
Press the MENU key until the word dAMP appears.
Step 2:
Press Enter
Step 3:
Press the
(up arrow key) or
(down arrow
key) to select a dampening option.
Step 4:
Press the ENTER key to finalize your Damp option.
(This Menu item is only seen on units with the switch option)
SWSET:
Allows for setting switch (relay) set points. The
gauge is offered with two SPDT switches (relays).
Step 1:
Press the MENU key.
Step 2:
Press the
(up arrow key) or
(down arrow
key) on the keypad to select the switch to be set. (If two
switches are present.)
Step 3:
Press ENTER. The top line of the gauge display will
indicate pressure at 60% of the fullscale gauge range* or
the most recent switch setpoint. The middle line of the dis-
play will indicate a bargraph that displays the pressure
position within the pressure range. The bottom line will
display SETPT (blinking).
*Indicates default.
MENU FUNCTIONS