ConsoliDator Multi-Channel Controller
Instruction Manual
10
4-20 mA Transmitter Outputs
OUTPUT RANGE
4.00 to 20.00 mA
CALIBRATION
Factory calibrated for 4-20 mA
SCALING RANGE
Any process range.
ASSIGNMENT &
OPERATION
Assign to any analog or pulse input channel for linear
scaling or for manually tuned PID control output.
ACCURACY
±0.05% F.S.
±
0.01 mA
TEMPERATURE DRIFT
50 PPM/
°
C from 0 to 50
°
C ambient.
Output & Input drifts are separate.
OUTPUT LOOP POWER
Self powered or externally powered by 12 to 32 VDC
OUTPUT LOOP
RESISTANCE
Powered by controller: 10 to 600
Ω
Powered by external 12 VDC: 10 to 300
Ω
Powered by external 24 VDC: 10 to 600
Ω
Powered by external 32 VDC: 10 to 900
Ω
ISOLATION
1500 V output-to-power line; 500 V output-to-input when
powered by external supply.
Modbus
®
Serial Communications
COMPATIBILITY
EIA-232
PROTOCOL
Modbus RTU
DEVICE ADDRESS
Programmable between 1 and 247
TRANSMIT DELAY
Programmable between 0 and 300 ms
BAUD RATE
Programmable from 1200 to 38400
DATA
8 bit (1 start bit, 1 stop bit)
PARITY
EVEN, NONE with 1 stop bit, or NONE with 2 stop bits.
ConsoliDator
®
Software
SYSTEM
REQUIREMENTS
Windows® 95/98/ME/NT4/2000/XP
COMPATABILITY
Separate versions for ConsoliDator 4 and ConsoliDator 8.
COMMUNICATION
RS-232 using null-modem serial cable.
LOGGING
REPORTS
Programmable between 1 sec. and 10 min.
LOGGING REPORT
Log to comma separated value (.csv) file compatible with
spreadsheet applications such as Microsoft® Excel.
CONFIGURATION
Configure inputs and outputs. Store ConsoliDator settings file on PC
for programming other controllers or restoring settings.
Compliance Information
UL LISTED
USA and Canada: UL 508 Industrial Control Equipment
UL FILE NUMBER
E160849