ConsoliDator Multi-Channel Controller
Instruction Manual
29
Multi-Point Linearization
Multi-Point Linearization must be configured using a PC and supplied ConsoliDator Monitor
Software. After communication has been established between PC and ConsoliDator, select
System Settings
from the software’s menu bar. Next, select a channel to set up from the
Analog Input Channels
drop-down menu and press
Edit Channel
. Select
[Multi-Point Linearization] from
Channel
Function
drop-down menu. Use
Add
,
Edit
, and
Del
to manipulate the
Multi-Point Data Table.
Continue with other settings in this menu and
press
Save
when complete. Reference
ConsoliDator Monitor Software
(page 51
)
for help
setting up the PC connection.
Sensor Input Setup
The simplest method is to assign low sensor input reading to a corresponding process
value (zero point) and then assign a high sensor input reading to a corresponding
process value (span.) The sensor input may be read from a live signal or entered
manually.
1. Select
Configure Sensor Input
.
2.
In the new box that appears move cursor to
Low Value
and press
EDIT
. Use the
arrows to enter a process value associated with a low sensor point. Press
SAVE
.
3.
Move cursor to
High Value
and press
EDIT
. Use the arrows to enter a process
value associated with a high sensor point. Press
SAVE
.
4.
Next, enter the
Sensor
points corresponding to the process values entered in
(2)-
(3)
– for example: 4.00 mA and 20.00 mA. To read a live signal corresponding
with the process value follow
(a.)
To enter a signal point manually follow
(b.)
a.
Verify connections and set transmitter to the appropriate level. Allow to
settle for a few seconds. Position cursor at the
Sensor
parameter –
located under the corresponding process value on the screen – and
press
LIVE
.
b.
To manually enter a signal level into the
Sensor
parameter
corresponding to the process value entered in
(2)
, position cursor in
front of
Sensor
– located under
Low Value
on the screen – and press
EDIT
. Use the arrow keys to enter a sensor value in mA. Press
SAVE
when completed.
5.
Verify entries and press
EXIT
.
Notes:
1. Controller requires a minimum span of 1 mA.
2. High and Low process values may be scaled in a negative direction for a decreasing process.
For example: 100 gal High Value at 4 mA Sensor and 0 gal High Value at 20 mA Sensor.