SuperNova PD500 PID Process & Temperature Controllers
Instruction Manual
47
G.CTL Parameter Details
Parameter
Setting range
Unit
Default
Value
Parameter Display Condition
AT.MD
STD, LOW
STD
G.OUT parameter CNT1 is PID or
G.OUT parameter CNT2 is PID.
AT
OFF, ON
OFF
G.OUT parameter CNT1 is PID or
G.OUT parameter CNT2 is PID.
Displays only in RUN mode.
ARW
Auto, (50.0 - 200.0) %
%
50.0
G.OUT parameter CNT2 is ONOF or
PID.
ALPA
0 – 100
50
G.OUT parameter CNT1 or CNT2
are set to PID.
1.PID
PID No 1 selection
G.OUT parameter CNT1 or CNT2
are set to PID.
1.P
EUS (0.15 - 100.0) % (Note 4)
EUS (0.0 - 100.0) % (Note 5)
Note 1
EUS 5.0 %
G.OUT parameter CNT1 is set to
PID.
1.I
OFF, 1 - 6000
Seconds
240
1.D
OFF, 1 - 6000
Seconds
60
1.MR
-5.0 - 105.0
%
50.0
G.OUT parameter CNT1 is set to
PID and 1.I is set to OFF.
1.Pc
EUS (0.0 - 100.0) %
Note 1
EUS 5.0 % G.OUT parameter CNT2 is set to
PID.
1.Ic
OFF, 1 - 6000
Seconds
240
1.Dc
OFF, 1 - 6000
Seconds
60
1.DB
-100.0 - 50.0
%
3.0
G.OUT parameter CNT1 is PID or
G.OUT parameter CNT2 is PID and
CNT2 is not set to NONE.
2.PID
PID No 2 selection
G.OUT parameter CNT1 is PID or
G.OUT parameter CNT2 is PID.
2.P
EUS (0.15 - 100.0) % (Note 4)
EUS (0.0 - 100.0) % (Note 5)
Note 1
EUS 5.0 %
G.OUT parameter CNT1 is set to
PID.
2.I
OFF, 1 - 6000
Seconds
240
2.D
OFF, 1 - 6000
Seconds
60
2.MR
-5.0 - 105.0
%
50.0
G.OUT parameter CNT1 is set to
PID and 1.I is set to OFF.
2.Pc
EUS (0.0 - 100.0) %
Note 1
EUS 5.0 % G.OUT parameter CNT2 is set to
PID.
2.Ic
OFF, 1 - 6000
Seconds
240
2.Dc
OFF, 1 - 6000
Seconds
60
2.DB
-100.0 - 50.0
%
3.0
G.OUT parameter CNT1 is PID or
G.OUT parameter CNT2 is PID and
CNT2 is not set to NONE.
3.PID
PID No 3 selection
G.OUT parameter CNT1 is PID or
G.OUT parameter CNT2 is PID.
3.P
EUS (0.15 - 100.0) % (Note 4)
EUS (0.0 - 100.0) % (Note 5)
Note 1
EUS 5.0 %
G.OUT parameter CNT1 is set to
PID
3.I
OFF, 1~6000
Seconds
240
3.D
OFF, 1~6000
Seconds
60
3.MR
-5.0 - 105.0
%
50.0
G.OUT parameter CNT1 is set to
PID and 3.I is set to OFF.
3.Pc
EUS (0.0 - 100.0) %
Note 1
EUS 5.0 % G.OUT parameter CNT2 is set to
PID
3.Ic
OFF, 1 - 6000
Seconds
240
3.Dc
OFF, 1~6000
Seconds
60
3.DB
-100.0 ~ 50.0
%
3.0
G.OUT parameter CNT1 is PID or
G.OUT parameter CNT2 is PID
and
CNT2 is not set to NONE.
4.PID
PID No 4 selection
G.OUT parameter CNT1 is PID or
G.OUT parameter CNT2 is PID.
4.P
EUS (0.15 - 100.0) % (Note 4)
EUS (0.0 - 100.0) % (Note 5)
Note 2
EUS 5.0 %
G.OUT parameter CNT1 is set to
PID.
4.I
OFF, 1 - 6000
Seconds
240
4.D
OFF, 1 - 6000
Seconds
60