SuperNova PD500 PID Process & Temperature Controllers
Instruction Manual
12
Alarm Relay Outputs
Function
Programmable for 13 different alarm
types or off.
Number
Two alarm relays standard on all
models.
Alarm Relay
Ratings
Rated resistive load switching capacity:
5 A, 250 VAC; 5 A, 30 VDC
Deadband
0-100% FS, user selectable
High or Low
Alarm
User may program any alarm for high,
low, or high-low range operation.
Absolute or
Deviation Alarm
User may program any alarm as an
absolute value alarm or a set value
deviation alarm.
Loop Break
Alarm
User may program any SUB alarm relay
as a loop break alarm.
Alarm Relay
Operation
•
Automatic (non-latching)
and/or manual reset
•
Latching (requires manual
acknowledge) with/without
clear
•
Off (disable unused relays)
Relay Reset
(Acknowledge)
Automatic, front panel button, in setup
parameter menu, or through serial
communications
Time Delay
0 to 999 seconds, on and off delays;
programmable for each SUB relay.
Fail-Safe
Operation
Programmable, independent for each
alarm relay. Relay coils are energized in
non-alarm condition. In case of power
failure, relays will go to alarm state.
Standby
Operation
Programming, independent for each
alarm relay
Auto
Initialization
When power is applied to the controller,
relays will reflect the state of the input to
the controller unless standby mode is
enabled.
4-20 mA Retransmit Output
Function
4-20 mA linear current output
Scaling Range
0-100% of full scale
Output Loop
Resistance
600 Ω max
imum load
Output Accuracy
±0.2% of full scale ± 1 digit
0-10 VDC Output
The
can convert the
optional 4-20 mA output to a 0-10 VDC
output
Remote SV Process Input
Function
Process input to remotely change SV
Input Type &
Range
1-5 V, 4-20 mA
External 250
Ω
resistor required to read
4-20 mA.
Input Accuracy
±0.2% of full scale ± 1 digit
USB Connection
Function
SuperNova software connection only
Location
PD510: Top, behind panel
PD520 & PD530: Front mounted behind
rubber seal, accessible from front panel
Communication
UMS (USB Mass Storage) 2.0
Compatibility
USB 2.0 Standard, Compliant
Connector Type
Mini-USB receptacle
Cable
USB A Male to Mini-USB Cable
Protocol
Protocol: PC-LINK
Baud rate: 38400 bps
Start bit: 1 bit
Data bits: 8 bits
Parity bit: None
Stop bit: 1 bit
Communication
Distance
16.4 ft (5 m) maximum
Digital Inputs
Function
Digital Input 1: Select Run/Stop Mode
Digital Input 2: Select SV 1 or SV4/REM
Contacts
DI1 and DI2, shared common
Logic Levels
On: 1.5 V; Off: 0.1 V
Input Current
Approximately 2 mA each contact
Input
Impedance
On : 1 kΩ max, Off: 100 kΩ min.
Open Contact
Voltage
Open contact voltage approximately
5 VDC