ProtEX-MAX PD8-6210 Explosion-Proof Analog Input Batch Controller
Instruction Manual
36
Display Functions and Messages
Display
Parameter
Action/Setting
Description
RSt 1
Reset 1
Program reset point 1
RLY 2
Relay 2
Relays 2-4 setup.
FaiLSF
Fail-safe
Enter
Fail-safe
menu
FLS 1
Fail-safe 1
Set relay 1 fail-safe
operation
on
On
Enable fail-safe operation
off
Fail-safe off
Disable fail-safe operation
DeLAY
Delay
Enter relay
Time Delay
menu
DLY 1
Delay 1
Enter relay 1 time delay
setup
On 1
On
Set relay 1 On time delay
OFF 1
Off
Set relay 1 Off time delay
break
Loop break
Set relay condition if loop
break detected
(For mA input only)
iGnorE
Ignore
Ignore loop break condition
(Processed as a low signal
condition)
On
On
Relay goes to alarm
condition when loop break
is detected
OFF
Off
Relay goes to non-alarm
condition when loop break
is detected
Aout
Analog
output
Enter the
Analog output
scaling menu
Dis 1
Display 1
Program display 1 value
Out 1
Output 1
Program output 1 value
(e.g. 4.000 mA)
Dis 2
Display 2
Program display 2 value
Out 2
Output 2
Program output 2 value
(e.g. 20.000 mA)
reset
Reset
Press Enter to access the
Reset
menu
Rst Hi
Reset high
Press Enter to reset max
display
Rst Lo
Reset low
Press Enter to reset min
display
Rst HL
Reset
high & low
Press Enter to reset max &
min displays
Rst t
Reset total
Press Enter to reset total
Rst Gt
Reset
grand total
Press Enter to reset grand
total
Rst bc
Reset
batch count
Press Enter to reset batch
count
Display Functions and Messages
Display
Parameter
Action/Setting
Description
Contrl
Control
Enter Manual Control menu
Auto
Automatic
Press Enter to set controller
for automatic operation
nmAn
Manual
Press Enter to manually
control relays or analog
output operation
`pass
Password
Enter the
Password
menu
Pass 1
Password 1
Set or enter Password 1
Pass 2
Password 2
Set or enter Password 2
Pass 3
Password 3
Set or enter Password 3
Total
Total
password
Set or enter password for
manual reset
Gtotal
Grand total
password
Set or enter password for
manual reset
nonrst
Non-
resettable
Non-resettable grand total
set
after entering “050873”
for Gtotal password
unloc
Unlocked
Program password to lock
controller
locd
Locked
Enter password to unlock
controller
999999
-99999
Flashing
display
Overrange condition
Underrange condition
•
During operation, only the STOP button will
function, to stop/pause the batch. As a result,
relay alarms cannot be manually reset.