ProtEX-MAX PD8-6210 Explosion-Proof Analog Input Batch Controller
Instruction Manual
32
Analog Output Transmitter Power
Supply
The internal 24 VDC power supply powering the
analog output may be used to power other devices if
the analog output is not used. The I+ terminal is the
+24 V and the R terminal is the return.
Figure 20. Analog Output Supply Powering Other
Devices
Remote Programming
The controller can be operated via the programming
buttons or a remote control station* with required
approvals to be located in a hazardous area using the
digital inputs.
* Control station must be approved for hazardous
locations
R
I-
I+
1
3
2
24 VDC
Powered
Device
24 V
+
-