PD154 & PD158 Vigilante
®
II Annunciators
Instruction Manual
34
ISA Sequence F1A
First-Out Indication with Acknowledge Pushbutton, No Lock-In of
Subsequent Alarms, and Automatic Reset
Momentary Alarm
Maintained Alarm
Sequence F1A
Sequence F1A Flowchart
Switch Positions
Condition
LED
Horn
Condition
LED
Horn
1
st
Pt Next Pt
1
st
Pt Next Pt
Normal
Off Off Off
Normal
Off Off Off
Alert
Flash Steady
On
Alert
Flash Steady
On
Normal
Flash Off On
ACK
Pushbutton
ACK
Pushbutton
Acknowledge
Steady Steady
Off
Acknowledge
Off Off Off
Normal
Off Off Off
Ack
Pressed
Condition
Normal
1
st
Pt LED
Off
Next Pt LED
Off
Horn
Off
Condition
Alert
1
st
Pt LED
Flash
Next Pt LED
Steady
Horn
On
Condition
Alert
1
st
Pt LED
Steady
Next Pt LED
Steady
Horn
Off
Alarm Condition
Return
to Normal
Ack
Pressed
Condition
Normal
1
st
Pt L D
Flash
Next Pt LED
Off
Horn
On
Return
to Normal