PD154 & PD158 Vigilante
®
II Annunciators
Instruction Manual
8
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.
General
DISPLAY
PD154; Four red LED channel/point indicators.
PD158; Eight red LED channel/point indicators.
One green LED power indicator.
ALARM
MESSAGES
Custom printed adhesive clear labels.
Area:
PD154, 1.25" x .60" (32 mm x 15 mm), 4 messages
PD158, 1.25" x .25" (32 mm x 6 mm), 8 messages
User specified size and length, up to 4 lines (PD154) or 2
lines (PD158) of 14 characters of size 9 fonts.
PROGRAMMING
METHODS
Rear 4-position switch for sequence selection and horn
operation. Three front panel pushbuttons for NO/NC input
selection, sequence options, and sequence operation.
NOISE FILTER
40 ms debounce on inputs (including SIL, ACK, and RST).
SHARED FIRST-
OUT SYSTEMS
1 ms unit-to-unit delay. Maximum of 200 units in the
shared first-out system.
NON-VOLATILE
MEMORY
All programmed settings are stored in non-volatile memory
for a minimum of ten years if power is lost.
POWER
OPTIONS
85-265 VAC, 50/60 Hz
90-265 VDC, 20 W max
or 12-36 VDC, 12-24 VAC, 6 W max
FUSE
Required external fuse: UL Recognized, 5 A max, slow
blow. Up to 6 annunciators may share one 5 A fuse
ISOLATED
POWER SUPPLY
24 VDC
10% @ 200 mA max
Standard on 85-265 VAC powered units only.
ISOLATION
4 kV input/output-to-power line.
OVERVOLTAGE
CATEGORY
Installation Overvoltage Category II:
Local level with smaller transient overvoltages than
Installation Overvoltage Category III
ENVIRONMENTAL
Operating temperature range: -40 to 65°C
Storage temperature range: -40 to 85°C
Relative humidity: 0 to 90% non-condensing
CONNECTIONS
Removable screw terminal blocks for 12 to 22 AWG wire.
ENCLOSURE
1/8 DIN, high impact plastic, UL 94V-0, front color: black
MOUNTING
1/8 DIN panel cutout required. Two panel mounting
bracket assemblies provided.