OPERATIONAL FEATURES

2   Built-in Digital Inputs/Outputs

The Helios comes with five digital inputs and four digital 

outputs. The digital inputs can operate with the interlock relays 

feature, force relays on from a signal from a PLC or relay on 

other equipment, and much more. The digital inputs can also 

be used to mimic the programming buttons, which are located 

behind a door and generally not accessible during operation. 

The digital outputs can be used to send signals to PLCs and 

other devices.

1   Three Buttons Under the Front Cover

The default settings for the function keys are:

F1

F2

F3

Reset Max/Min 

Reading

Display Max/Min 

Reading

Acknowledge 

Relays

Function Keys, F4 Terminal, Digital Inputs 

There are two ways the user can interact with the Helios to 

perform a variety of useful functions:

V+ V- F4 COM

2

1

4

3

2

1

I+

I-

O1 O2 O3 O4 G

I

1

I

2

I

3

I

4

+5

Ground

5 VDC

4 Digital Inputs 

& 4 Digital Outputs

F4 Terminal for  

Digital Input

Remote Operation of Front Panel Buttons

The Helios’s programming buttons are located behind a door 

and generally not accessible during operation. Digital inputs 

are provided that can be wired to remote buttons to operate 

the programming buttons in a convenient location. MeterView 

Pro provides an easy way to do this programming:

Max / Min Display

Max/Min (or Peak/Valley) is standard on the Helios PD2-6400. 

Either display can be configured to show either maximum or 

minimum excursion since last reset. The displays can also 

be configured to toggle between Max and Min values. Both 

values can be simply reset from the front panel.

Click here to watch the  

Function Keys video

Helios PD2-6400

High Voltage & Current Meter

The Control Station allows for remote control of the PD2-6400’s

four buttons behind the front panel door.

I

1

I

2

I

3

I

4

+5

Connector blocks located behind front panel door

PDA2364-MRUE

Control Station

Remote Operation Using PDA2364-MRUE Control Station

The PD2-6400's four internal programming and operations buttons can be remotely controlled by using the PDA2364-MRUE  

4-button control station accessory as shown in the diagram below.

Содержание Helios PD2-6400

Страница 1: ...Programming Software Super Bright Display Operating Temperature Range 40 to 65 C 40 to 150 F UL C UL Listed E160849 508 Industrial Control Equipment Input Power Options Include 85 265 VAC or 12 24 VD...

Страница 2: ...ANCED DISPLAY FEATURES 4 QUICK EASY SCALE PROGRAMMING METHODS 5 4 20 MA OUTPUT RELAYS 8 APPLICATION EXAMPLES 11 DIGITAL COMMUNICATIONS 13 ON BOARD DIGITAL INPUTS AND OUTPUTS 13 PHYSICAL FEATURES 14 OP...

Страница 3: ...ally all these features and capabilities can easily be programmed with free MeterView Pro PC based software Precision Digital also offers several accessories for the Helios to enhance the user experie...

Страница 4: ...urrently set to 95 00 Display Voltage and Current Individually or at Same Time The Helios PD2 6400 can accept both a voltage and a current input These can be displayed as one or the other as illustrat...

Страница 5: ...ompleted it can be locked with a password Free PC Based MeterView Pro USB Programming Software Cable The Helios comes preloaded with free MeterView Pro programming software that connects and installs...

Страница 6: ...eters Set Analog Output Values Enable Manual Control Test Relays Digital Outputs Setup Screen Set Scale Values Set the Number of Points up to 32 Import from Excel Export to Excel Programming Screen Gr...

Страница 7: ...10 Communications Onboard USB firmware version 4 0 or higher RS 232 Adapter or RS 485 Adapter Meter Address 1 247 Reports Data logging Save as CSV file format Configuration Save as PDC file format or...

Страница 8: ...set up for reverse scaling as shown below the output will be 4 00 mA when the display reads 150 0 and the output will be 20 00 mA when the display reads 0 Front Panel Push Button Programming The 4 20...

Страница 9: ...inals F4 and Common Latching Alarm must be reset manually and can be done so at any time with a switch wired across terminals F4 and Common Latching with Reset after Cleared Alarm must be reset manual...

Страница 10: ...en the PV reaches that set point it will close that relay s contacts for a preset period of time 0 1 to 5999 9 seconds Switching Inductive Loads The use of suppressors snubbers is strongly recommended...

Страница 11: ...few of the PD2 6400 s application capabilities using generators and transformers Each example is followed by a wiring diagram that shows proper switch position for the meter Voltage Input Application...

Страница 12: ...vailable in ranges of 100 200 400 600 and 1000 AAC These nonintrusive devices feature split core convenience for easy installation and are a cost effective solution for monitoring load or proof of ope...

Страница 13: ...ers click here PDA7485 I RS 232 to RS 422 485 Isolated Converter PDA8485 I USB to RS 422 485 Isolated Converter All adapters and connectors supplied with appropriate cables Modbus PV Input Remote Mess...

Страница 14: ...in industrial applications where it will be exposed to wet dusty hot cold and other adverse conditions The Helios is housed in a rugged NEMA 4X enclosure can operate over a wide temperature range incl...

Страница 15: ...e Range The Helios can operate from 40 to 65 C 40 to 150 F meaning it can be installed in a wide variety of indoor and outdoor industrial applications And over this range the Helios will drift no more...

Страница 16: ...nal for Digital Input Remote Operation of Front Panel Buttons The Helios s programming buttons are located behind a door and generally not accessible during operation Digital inputs are provided that...

Страница 17: ...rol or to return them to automatic operation Click here to watch the Meterview Pro video Custom Tags i e Power Custom Units i e Amps Volts Alarm Status Indicators Plastic Control Stations For The Heli...

Страница 18: ...nue to be calculated in the background FK DI Ln1 Hi Display maximum display value on line 1 FK DI Ln1 Lo Display minimum display value on line 1 FK DI Ln1 HL Display maximum minimum display values on...

Страница 19: ...V F4 COM 2 1 4 3 2 1 I I AC TYPE DC CONNECTIONS Connector Labeling for Fully Loaded PD2 6400 DIMENSIONS Mounting Hole Mounting Hole Connection Cover Screw 10 63 270 12 59 319 7 2 63 67 4 77 121 2 2600...

Страница 20: ...d Enclosure Operating Temperature of 40 to 65 C Now UL and C UL Approved LARGE DISPLAYS Helios Series IECEx Big Bright Displays For Indoor or Outdoor in Bright Sunlight 24 VDC Transmitter Power Supply...

Страница 21: ...plastic case color gray Includes four PG11 through hole conduit openings with two factory installed PG11 IP68 black nylon threaded hole plugs with backing nuts Wall Mounting Four 4 mounting holes prov...

Страница 22: ...r none with 1 or 2 stop bits Byte to Byte Timeout 0 01 2 54 seconds Turn Around Delay Less than 2 ms fixed Note Refer to the HeliosRegister Tables located at www predig com for details Isolated 4 20 m...

Страница 23: ...mation contained in this document is subject to change without notice Precision Digital Corporation makes no representations or warranties with respect to the contents hereof and specifically disclaim...

Отзывы: