Helios Large Display Pulse Input Batch Controller Instruction Manual
PD2-6310
7
Batch Total &
Grand Total
Display
0 to 999,999; automatic lead zero
blanking. “T” LED is illuminated while
displaying batch total. “GT” LEDs are
illuminated while displaying grand
total. Up to 999,999 for batch
total/preset. Up to 999,999,999 with
grand total-overflow feature. “
oF
” is
displayed to the left of grand total
overflow and ▲ LED is illuminated.
Batch Total
Decimal
Point
Up to five decimal places or none:
d
.
ddddd
,
d
.
dddd
,
d
.
ddd
,
d
.
dd
,
d
.
d
, or
dddddd
Total decimal point is independent of
rate decimal point.
Totalizer
Calculates total based on rate and
field programmable multiplier to
display total in engineering units.
Time base must be selected
according to the time units in which
the rate is displayed.
Grand
Totalizer
Rollover
Grand totalizer rolls over when
display exceeds 999,999,999. Relay
status reflects display.
Grand Total
Alarms
Up to seven, user selectable under
setup menu. Any set point can be
assigned to grand total and may be
programmed anywhere in the range
of the controller for grand total alarm
indication. Relay 1 should always be
assigned to batch.
Programmabl
e Delay
On Release
0.1 and 999.9 seconds; applied to
the first relay assigned to total or
grand total.
If the controller is programmed to
reset total to zero automatically when
the preset is reached, then a delay
will occur before the total is reset.
Grand Total
Reset
Via front panel button, external
contact closure on digital inputs,
automatically via user selectable
preset value and time delay, or
through serial communications.
Grand Total
Reset
Password
Grand total passwords may be
entered to prevent resetting the
grand total from the front panel.
Non-
Resettable
Grand Total
The grand total can be programmed
as a non-resettable total by entering
the password “050873”.
Caution!
Once the Grand Total has
been programmed as
“non-resettable” the
feature
cannot
be
disabled.
1
Alarms are active only when the batch is running.
Relays
Rating
2 or 4 SPDT (Form C) internal
and/or 4 SPST (Form A) external;
rated 3 A @ 30 VDC and 125/250
VAC resistive load; 1/14 HP (
≈
50
W) @ 125/250 VAC for inductive
loads
Noise
Suppression
Noise suppression is recommended
for each relay contact switching
inductive loads; see page 16 for
details.
Deadband
0-100% of span, user
programmable
High or Low
Alarm
User may program any alarm for
high or low trip point.
Unused alarm LEDs and relays may
be disabled (turn off).
Relay
Operation
Primary Functions:
Batch Control
Automatic (non-latching)
1
Sampling (based on time)
Off (disable unused relays and
enable Interlock feature)
Manual on/off control mode
Secondary Functions
2
:
Pump alternation control (2 to 4
relays)
Latching (requires manual
acknowledge)
Relay Reset
User selectable via front panel
buttons or digital inputs
1. Automatic reset only (non-
latching), when the input
passes the reset point.
2. Aut manual reset at any
time (non-latching)
3. Manual reset only, at any time
(latching)
4. Manual reset only after alarm
condition has cleared (latching)
Note: Front panel button or digital
input may be assigned to
acknowledge relays
programmed for manual
reset.
Alarm Time
Delay
0 to 999.9 seconds, on & off relay
time delays
Programmable and independent for
each relay
Fail-Safe
Operation
Programmable and independent for
each relay.
Note: Relay coil is energized in non-
alarm condition. In case of
power failure, relay will go to
alarm state.
Alarm Auto
Initialization
When power is applied to the
controller, relays will reflect the
state of the input to the controller.
Isolated 4-20 mA Transmitter Output
Output
Source
Process variable (PV), max, min, set
points 1-8, Modbus input, or manual
control mode
2
These functions are not functional when the unit is
being used as a batch controller with total set to yes.
!