Helios Large Display Pulse Input Batch Controller Instruction Manual
PD2-6310
31
Setting up the Batch Controller (
setup
)
The
Setup
menu is used to select:
1. Input signal the controller will
accept
2. Totalizer and batching
features
3. Display units/tags
4. Decimal point position
5. Program menu for scaling or
calibration
6. Display parameter and
intensity
7. Relay operation
8. 4-20 mA analog output
scaling
Press the Enter button to access any
menu or press Up arrow button to
scroll through choices. Press the
Menu button to exit at any time.
Setting the Input Signal
(
Input
)
There is a switch, located to the right
of the input connector, which must be
configured according to the input
level and type. Jumper J4 located
inside the controller, behind the input
signal connector, is used to select
the excitation voltage (24 V*, 10 V or
5 V) which is supplied to the P+ and
P- wiring terminals.
The controller may be calibrated
using the
K-Factor
function. Most
flowmeter manufacturers provide this information with the device. Enter the
K-Factor
(
Factor
) menu and
select the decimal point with highest resolution possible and program the K-factor value (
i.e.
pulses/gal).
The controller will automatically calculate the flow rate using the K-factor and the time base selected.
*
Default setting
Setting the Totalizer and Batching Features (
total
)
To simply not display the total, select alternative display parameters in the display (
dsplay
) menu.
Enable or disable the totalizer and batching features by selecting “
Yes
” or “
no
” after the input type has
been set up. If the totalizer features are disabled, all the totalizer and batching features and functions are
hidden from the menus.